Control command
Description
Test mode
Test with small load
The test mode function "Test with small load" provides a way of
checking the wiring of the control and main circuit with the aid of
a small motor (test motor).
• Activate
• Deactivate
You will find more information in chapter Test with small load
(Page 222).
Simulation
1), 3)
With the test mode function "Simulation", the 3RW55 soft starter
virtually simulates the motor operating states (starting, running,
stopping) without main current.
• Activate
• Deactivate
You will find more information in chapter Simulation (Page 224).
PIQ-DQ Bit 1.0 (output 1)
Activates or deactivates the control command concerned.
Requirement: The output action "Control source PIQ-DQ x.y Out‐
put n" is assigned to a digital output.
• 3RW55 soft starter: You can assign the control commands "Out‐
put 1", "Output 2" and "Output 3" to the digital outputs 1, 2
and 4 of the 3RW55 soft starter in any order via the digital out‐
put actions.
• 3RW55 Failsafe soft starter: You can assign the control com‐
mands "Output 1" and "Output 2" to the digital outputs 1 and 2
of the 3RW55 Failsafe soft starter in any order via the digital
output actions.
You will find more information in chapter Digital outputs
(Page 198).
PIQ-DQ Bit 1.1 (output 2)
PIQ-DQ Bit 2.0
1)
(output 3)
1)
Function is not available for the 3RW55 Failsafe soft starter.
2)
For 3RW55 soft starter from firmware version V2.1
3)
For 3RW55 soft starter from firmware version V2.0
8.22
Overview
Operating principle
The "Overview" menu displays the connected components and their device-related information
(I&M data).
Note
Device-related information
Note that it is only possible to edit the displayed device name of the 3RW55 or 3RW55 Failsafe
soft starter via the 3RW5 HMI High Feature.
Functions
8.22 Overview
SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters
234