Procedure
1. Plug the micro SD card into the 3RW5 HMI High Feature.
2. Transfer the data to the devices (3RW55 or 3RW55 Failsafe soft starter, 3RW5 HMI High
Feature, 3RW5 communication module).
Menu: "Micro SD card > Device change"
Note
Device change
The current data of all devices (3RW55 or 3RW55 Failsafe soft starter, 3RW5 HMI High
Feature, 3RW5 communication module) is overwritten by the data on the micro SD card.
3. Check the transferred data.
Result
You have transferred your saved data to your devices (3RW55 or 3RW55 Failsafe soft starter,
3RW5 HMI High Feature, 3RW5 communication module) with the "Device change" function.
10.6.2
Device change with SIRIUS Soft Starter ES (TIA Portal)
Requirements
• Accessories (optional), e.g. 3RW5 PROFINET or PROFIBUS communication module
• Connection of the 3RW55 or 3RW55 Failsafe soft starter to SIRIUS Soft Starter ES (TIA Portal).
The 3RW55 or 3RW55 Failsafe soft starter must not be connected online to SIRIUS Soft Starter
ES (TIA Portal).
• Project in SIRIUS Soft Starter ES (TIA Portal) with saved data (identical type)
Button: "Upload from device" on the toolbar.
In the "Project Navigation" window, the 3RW55 or 3RW55 Failsafe soft starter must be
selected in the current project so that the button can be operated.
Procedure
1. Transfer the data to the devices (3RW55 or 3RW55 Failsafe soft starter, 3RW5 HMI High
Feature, 3RW5 communication module) with SIRIUS Soft Starter ES (TIA Portal).
Button: "Download to device" on the toolbar.
In the "Project Navigation" window, the 3RW55 or 3RW55 Failsafe soft starter must be
selected in the current project so that the button can be operated.
Note
Device change
The data of all devices (3RW55 or 3RW55 Failsafe soft starter, 3RW5 HMI High Feature, 3RW5
communication module) is overwritten by the transferred data.
2. Check the transferred data.
Maintenance and service
10.6 "Device change" function
SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters
Equipment Manual, 02/2022, A5E35630887002A/RS-AF/006