Input action
Description
Factory setting
DI1
DI2
DI3
DI4
Motor
CCW
with parameter set 1
This function is active only when the "Creep speed" pa‐
rameter or reversing mode with external reversing switch‐
ing elements is active at the same time. The motor starts
with the values stored in the "Creep speed parameters"
menu item (with rotation opposite to the line phase direc‐
tion).
-
-
-
-
with parameter set 2
-
-
-
-
with parameter set 3
-
-
-
-
Motor standstill
1)
The 3RW55 soft starter evaluates the signal from an external motor
standstill detection at the input.
You will find more information in chapter External motor standstill de‐
tection (Page 162).
-
-
-
-
Use alternative stop‐
ping mode
You will find more information in chapter Alternative stopping
(Page 163).
-
-
-
-
Start pump cleaning
You will find more information in chapter Pump cleaning function
(Page 182).
-
-
-
-
1)
Input action is not available for the 3RW55 Failsafe soft starter.
8.12.2
Process data and process images
The basic functions of the 3RW55 and 3RW55 Failsafe soft starters are controlled and monitored
in the process data in the process images.
The process images can be transferred as follows:
• Cyclically in the fieldbus protocol
• Acyclically using data sets
Process image input (PII) and process image output (PIQ)
The following process images are transferred:
• Process image input with 16 bytes
• Process image output with 4 bytes
The tables for the process images describe only the supported process data. Inputs and outputs
that are not listed are not assigned.
Process image input (PII)
Process data
Process image
DI 0.0
Ready (automatic)
DI 0.1
Motor On
DI 0.2
Group error
DI 0.3
Group warning
DI 0.4
Input 1
DI 0.5
Input 2
Functions
8.12 Inputs
SIRIUS 3RW55 and 3RW55 Failsafe Soft Starters
196