Error
Cause
Remedy
Bypass protective shutoff
In bypass operation the current was
too high. Fault resetting is only possi‐
ble after cooling down.
• Check motor.
• Check dimensioning of the soft starter.
• Acknowledgment after cooling down. The
acknowledgment depends on the "Re‐
sponse to overload switching element" pa‐
rameter that has been set.
Switching element L1 failed
Switching element defective
Switch off the power supply (control supply
voltage) for at least 5 seconds and switch it on
again. If the fault is still present proceed as fol‐
lows:
• Please contact Technical Support (Support
• Check the switching elements for L1, L2,
and L3 and replace any that are defective.
Switching element L2 failed
Switching element L3 failed
Phase control failure
1. Error appears without motor
start:
– Motor incorrectly connected
– Inside-delta circuit incorrectly
realized
– Ground fault
2. Error appears while motor is start‐
ing:
– Kick start voltage too high
– Breakaway pulse incorrectly
set
1. Check and correct the wiring.
2. Adjust parameters or extend pause time.
Current measuring range exceeded
• With sensors: The measured val‐
ue has exceeded the range limits.
• With actuators: The output value
has exceeded an upper limit.
Check the interaction between the module and
the sensor or actuator.
Device error
Unrecoverable error detected after
internal diagnostics (self-test, contac‐
tor contacts, switching element,
etc.).
Switch off the power supply (control supply
voltage) for at least 5 seconds and switch it on
again. If the device error is still present proceed
as follows:
• Please contact Technical Support (Support
• Replace the device.
FW update faulty
The firmware is incomplete and / or
the firmware expansions are incom‐
plete or incompatible.
• Run a complete firmware update.
• Check any occurring error messages.
• Check to see whether or not the firmware
update was aborted.
Switching frequency time not kept
The maximum number of starting op‐
erations in the monitoring period has
been exceeded.
The next starting operation should take place
only after the interlock time has expired.
Main power rotation faulty
The direction of rotation field is not
correct.
-
Messages and diagnostics
9.4 Errors and remedial actions of the 3RW55 and 3RW55 Failsafe soft starters