Functions
2.16 Breaker Failure Protection 50BF
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
280
Monitoring of the Circuit Breaker Auxiliary Contacts
Evaluation of the circuit breaker's auxiliary contacts depends on the type of contacts, and how they are con-
nected to the binary inputs:
• the auxiliary contacts for circuit breaker "open" (4602
„>52-b“
) and "closed" (4601
„>52-a“
) are config-
ured,
• only the auxiliary contact for circuit breaker "open" is configured(4602
„>52-b“
),
• only the auxiliary contact for circuit breaker "closed" is configured(4601
„>52-a“
),
• none of the two auxiliary contacts is configured.
Feedback information of the auxiliary status of the circuit breaker is evaluated, depending on the allocation of
binary inputs and auxiliary contacts. After a trip command has been issued it is the aim to detect — if possible
— by means of the feedback of the circuit breaker's auxiliary contacts whether the breaker is open or in inter-
mediate position. If valid, this information can be used for a proper initiation of the breaker failure protection
function.
The logic diagram illustrates the monitoring of the circuit breaker's auxiliary contacts.
Figure 2-103
Logic diagram for breaker failure protection, monitoring of the circuit-breaker auxiliary contacts
Logic
If breaker failure protection is initiated, an alarm message is generated and a settable delay time is started. If
once the time delay has elapsed, criteria for a pickup are still met, a trip signal is issued to a superordinate
circuit breaker. Therefore, the trip signal issued by the circuit breaker failure protection is configured to one of
the output relays.
The following figure shows the logic diagram for the breaker failure protection function. The entire breaker
failure protection function may be turned on or off, or it can be blocked dynamically via binary inputs.
If the criteria that led to the pickup are no longer met when the time delay has elapsed, such pickup thus drops
out and no trip signal is issued by the breaker failure protection function.
To protect against nuisance tripping due to excessive contact bounce, a stabilization of the binary inputs for
external trip signals takes place. This external signal must be present during the entire period of the delay time,
otherwise the timer is reset and no trip signal is issued.