Appendix
A.8 Settings
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
646
7151
50N-1
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
50N-1
7152
50-2
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
50-2
7153
50N-2
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
50N-2
7154
51
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
51
7155
51N
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
51N
7156
67-1
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
67-1
7157
67N-1
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
67N-1
7158
67-2
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
67-2
7159
67N-2
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
67N-2
7160
67 TOC
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
67 TOC
7161
67N TOC
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
67N TOC
7162
sens Ground Flt
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
(Sensitive) Ground Fault
7163
46
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
46
7164
BINARY INPUT
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
Binary Input
7165
3Pol.PICKUP BLK
79M Auto Recl.
YES
NO
NO
3 Pole Pickup blocks 79
7166
50-3
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
50-3
7167
50N-3
79M Auto Recl.
No influence
Starts 79
Stops 79
No influence
50N-3
7200
bef.1.Cy:50-1
79M Auto Recl.
Set value T=T
instant. T=0
blocked T=
∞
Set value T=T
before 1. Cycle: 50-1
7201
bef.1.Cy:50N-1
79M Auto Recl.
Set value T=T
instant. T=0
blocked T=
∞
Set value T=T
before 1. Cycle: 50N-1
7202
bef.1.Cy:50-2
79M Auto Recl.
Set value T=T
instant. T=0
blocked T=
∞
Set value T=T
before 1. Cycle: 50-2
7203
bef.1.Cy:50N-2
79M Auto Recl.
Set value T=T
instant. T=0
blocked T=
∞
Set value T=T
before 1. Cycle: 50N-2
7204
bef.1.Cy:51
79M Auto Recl.
Set value T=T
instant. T=0
blocked T=
∞
Set value T=T
before 1. Cycle: 51
7205
bef.1.Cy:51N
79M Auto Recl.
Set value T=T
instant. T=0
blocked T=
∞
Set value T=T
before 1. Cycle: 51N
Addr.
Parameter
Function
C
Setting Options
Default Setting
Comments