Mounting and Commissioning
3.1 Mounting and Connections
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
421
Jumpers X71, X72 and X73 on the B–I/O-2 board serve to set up the
bus address
. The jumpers must not be
changed. The following two tables list the jumper presettings.
The mounting locations are shown in Figures 3-5 and 3-6.
Bus Addresses
Table 3-22
Jumper settings of
bus addresses
of input/output modules B-I/O-2 for 7SJ64 housing size
1
/
2
Table 3-23
Jumper settings of
bus addresses
of input/output modules B-I/O-2 for 7SJ64 housing size
1
/
1
Jumper
Mounting Location
Slot 19
X71
1-2
X72
2-3
X73
1-2
Jumper
Mounting Location
Slot 19 right side
Slot 33 left side
X71
2-3 1-2
X72
1-2 2-3
X73
1-2
1-2