Appendix
A.1 Ordering Information and Accessories
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
553
A.1.1.2 7SJ64 V4.7
1)
230 VAC only possible with release 7SJ64**...../
CC
and higher
Multi-Functional
Protective Relay with
Local Control
6
7
8
9
10 11 12
13 14 15 16
Supplemen-
tary
7
S
J
6
4
–
–
+
Housing, Inputs and Outputs, Measuring Transducer
Pos. 6
Housing
1
/
3
19'', 4-line Display, 7 BI, 5 BO, 1 Live Status Contact; 9th position only with: B, D, E
0
Housing
1
/
2
19'', Graphic Display, 15 BI, 13 BO, 1 Live Status Contact
1
Housing
1
/
2
19'', Graphic Display, 20 BI, 8 BO, 2 High-duty relays (4 Contacts), 1 Live Status Contact
2
Housing
1
/
1
19'', Graphic Display, 33 BI, 11 BO, 4 High-duty relays (8 Contacts), 1 Live Status Contact
5
Housing
1
/
1
19'', Graphic Display, 48 BI, 21 BO, 4 High-duty relays (8 Contacts), 1 Live Status Contact
7
Measuring Inputs (4 x V, 4 x
I
)
Pos. 7
I
Ph
= 1 A,
I
N
= 1 A (min. = 0.05 A); 15th position only with A, C, E, G
1
I
Ph
= 1 A,
I
N
= sensitive (min. = 0.001 A); 15th position only with B, D, F, H
2
I
Ph
= 5 A,
I
N
= 5 A (min. = 0.25 A); 15th position only with A, C, E, G
5
I
Ph
= 5 A,
I
N
= sensitive (min. = 0.001 A); 15th position only with B, D, F, H
6
I
Ph
= 5 A,
I
N
= 1 A (min. = 0.05 A); 15th position only with A, C, E, G
7
Power Supply, Binary Input Pickup Threshold Setting
Pos. 8
24 to 48 VDC, Binary Input Threshold 19 VDC
2
60 to 125 VDC, Binary Input Threshold 19 VDC
4
110 to 250 VDC, 115 to 230 VAC
, Binary Input Threshold 88 VDC
5
Construction
Pos. 9
Surface-mounting case, plug-in terminals, detached operator panel Installation in a low-voltage compartment
A
Surface-mounting case for panel, 2 tier terminals top/bottom
B
Surface-mounting case, screw-type terminals (direct connection / ring and spade lugs), detached operator
panel, installation in a low-voltage
C
Flush mounting case with plug-in terminals (2/3 pin connector)
D
Flush mounting case, screw-type terminals (direct connection / ring and spade lugs)
E
Surface-mounting case, screw-type terminals (direct connection / ring and spade lugs), without operator panel,
installation in a low-voltage
F
Surface-mounting case, plug-in terminals, without operator panel Installation in a low-voltage compartment
G
Region-specific Default / Language Settings and Function Versions
Pos. 10
Region DE, 50 Hz, IEC, Language German (Language can be changed)
A
Region World, 50/60 Hz, IEC/ANSI, language English (language can be changed)
B
Region US, 60 Hz, ANSI/IEC, Language American English (Language can be changed)
C
Region FR, 50/60 Hz, IEC/ANSI, Language French (Language can be changed)
D
Region World, 50/60 Hz, IEC/ANSI, Language Spanish (Language can be changed)
E
Region World, 50/60 Hz, IEC/ANSI, Language Italian (Language can be changed)
F
www
. ElectricalPartManuals