Mounting and Commissioning
3.1 Mounting and Connections
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
423
Pickup Voltages of BI8 to BI15 for 7SJ641*-
Table 3-24
Jumper settings for the
pickup voltages
of the binary inputs BI8 to BI15 on the C–I/O-1 board
for model 7SJ64
1
*-
1)
Factory settings for devices with power supply voltages of 24 VDC to 125 VDC
2)
Factory settings for devices with power supply voltages of 110 to 220 VDC and 115 VAC or 115 to 230 VAC
3)
Use only with pickup voltages 220 or 250 VDC
Contact Mode
With models 7SJ64
1
binary output BO6 can be changed from normally open to normally closed operation. The
following table shows the setting of jumper X40 regarding the
contact mode
.
Table 3-25
Jumper settings for
contact mode
of the binary output BO6 on the C–I/O-1 board
PCB Addresses
Jumpers X71, X72 and X73 on the input/output board C-I/O-1 are used to set the bus address and must not be
changed. The following table lists the jumper presettings.
The slots of the boards are shown in Figure 3-5.
Table 3-26
Jumper Settings of
Module Addresses
of C–I/O-1 board for 7SJ64
Binary Inputs
Jumper
19 VDC Pickup
88 VDC Pickup
176 VDC Pickup
BI8
X21/X22
L
M
H
BI9
X23/X24
L
M
H
BI10
X25/X26
L
M
H
BI11
X27/X28
L
M
H
BI12
X29/X30
L
M
H
BI13
X31/X32
L
M
H
BI14
X33/X34
L
M
H
BI15
X35/X36
L
M
H
Jumper
Open in quiescent state (NO)
Closed in quiescent state (NC)
Presetting
X40
1-2
2-3
1-2
Jumper
Presetting
X71
H
X72
L
X73
H
www