![Siemens SIPROTEC 7SJ62 Скачать руководство пользователя страница 404](http://html.mh-extra.com/html/siemens/siprotec-7sj62/siprotec-7sj62_manual_382149404.webp)
Mounting and Commissioning
3.1 Mounting and Connections
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
404
Power Supply
Table 3-2
Jumper settings for the nominal voltage of the integrated
power supply
on the processor board
A–CPU to 7SJ62.../DD
Pickup Voltages of BI1 to BI3
Table 3-3
Jumper settings for the
pickup voltages
of the binary inputs BI1 to BI3 on the processor board
A–CPU to 7SJ62.../DD
1)
Factory settings for devices with power supply voltages of 24 VDC to 125 VDC
2)
Factory settings for devices with power supply voltages of 110 VDC to 220 VDC and 115/230 VAC
Jumper
Rated Voltage
60 to 125 VDC
110 to 250 VDC
115 VAC
24/48 VDC
230 VAC
X51
1-2
2-3
Jumpers X51 to X53 are not used
X52
1-2 and 3-4
2-3
X53
1-2
2-3
interchangeable
cannot be changed
Binary Inputs
Jumper
19 VDC Pickup
BI1
X21
L
H
BI2
X22
L
H
BI3
X23
L
H
www