![Siemens SIPROTEC 7SJ62 Скачать руководство пользователя страница 652](http://html.mh-extra.com/html/siemens/siprotec-7sj62/siprotec-7sj62_manual_382149652.webp)
Appendix
A.8 Settings
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
652
9096
RTD 9 STAGE 2
RTD-Box
-58 .. 482 °F;
∞
248 °F
RTD 9: Temperature Stage 2
Pickup
9101A
RTD10 TYPE
RTD-Box
Not connected
Pt 100
Ω
Ni 120
Ω
Ni 100
Ω
Not connected
RTD10: Type
9102A
RTD10 LOCATION
RTD-Box
Oil
Ambient
Winding
Bearing
Other
Other
RTD10: Location
9103
RTD10 STAGE 1
RTD-Box
-50 .. 250 °C;
∞
100 °C
RTD10: Temperature Stage 1
Pickup
9104
RTD10 STAGE 1
RTD-Box
-58 .. 482 °F;
∞
212 °F
RTD10: Temperature Stage 1
Pickup
9105
RTD10 STAGE 2
RTD-Box
-50 .. 250 °C;
∞
120 °C
RTD10: Temperature Stage 2
Pickup
9106
RTD10 STAGE 2
RTD-Box
-58 .. 482 °F;
∞
248 °F
RTD10: Temperature Stage 2
Pickup
9111A
RTD11 TYPE
RTD-Box
Not connected
Pt 100
Ω
Ni 120
Ω
Ni 100
Ω
Not connected
RTD11: Type
9112A
RTD11 LOCATION
RTD-Box
Oil
Ambient
Winding
Bearing
Other
Other
RTD11: Location
9113
RTD11 STAGE 1
RTD-Box
-50 .. 250 °C;
∞
100 °C
RTD11: Temperature Stage 1
Pickup
9114
RTD11 STAGE 1
RTD-Box
-58 .. 482 °F;
∞
212 °F
RTD11: Temperature Stage 1
Pickup
9115
RTD11 STAGE 2
RTD-Box
-50 .. 250 °C;
∞
120 °C
RTD11: Temperature Stage 2
Pickup
9116
RTD11 STAGE 2
RTD-Box
-58 .. 482 °F;
∞
248 °F
RTD11: Temperature Stage 2
Pickup
9121A
RTD12 TYPE
RTD-Box
Not connected
Pt 100
Ω
Ni 120
Ω
Ni 100
Ω
Not connected
RTD12: Type
9122A
RTD12 LOCATION
RTD-Box
Oil
Ambient
Winding
Bearing
Other
Other
RTD12: Location
9123
RTD12 STAGE 1
RTD-Box
-50 .. 250 °C;
∞
100 °C
RTD12: Temperature Stage 1
Pickup
9124
RTD12 STAGE 1
RTD-Box
-58 .. 482 °F;
∞
212 °F
RTD12: Temperature Stage 1
Pickup
9125
RTD12 STAGE 2
RTD-Box
-50 .. 250 °C;
∞
120 °C
RTD12: Temperature Stage 2
Pickup
9126
RTD12 STAGE 2
RTD-Box
-58 .. 482 °F;
∞
248 °F
RTD12: Temperature Stage 2
Pickup
Addr.
Parameter
Function
C
Setting Options
Default Setting
Comments
www
. ElectricalPartManuals