Functions
2.2 Overcurrent Protection 50, 51, 50N, 51N
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
64
The following table gives an overview of the interconnection to other functions of 7SJ62/64.
Table 2-1
Interconnection to other functions
2.2.2
Definite Time, High-set Elements 50-3, 50-2, 50N-3, 50N-2
For each element an individual pickup value
50-3 PICKUP
,
50-2 PICKUP
or
50N-3 PICKUP
,
50N-2
PICKUP
is set. For
50-3 PICKUP
and
50N-3 PICKUP
, apart from
Fundamental
and
True RMS
, the
Instantaneous
values can also be measured. Each phase and ground current is compared separately per
element with the common pickup values
50-3 PICKUP
,
50-2 PICKUP
or
50N-3 PICKUP
,
50N-2 PICKUP
.
If the respective pickup value is exceeded, this is signaled. After the user-defined time delays
50-3 DELAY
,
50-2 DELAY
or
50N-3 DELAY
,
50N-2 DELAY
have elapsed, trip signals are issued which are available for
each element. The dropout value is roughly equal to 95% of the pickup value for currents > 0.3
I
Nom
. If the mea-
surement of the instantaneous values has been configured for the 50-3 or 50N-3 element, the dropout ratio
amounts to 90 %.
Pickup can be stabilized by setting dropout times
1215
50 T DROP-OUT
or
1315
50N T DROP-OUT
. This
time is started and maintains the pickup condition if the current falls below the threshold. Therefore, the function
does not drop out at high speed. The trip delay time
50-3 DELAY
,
50-2 DELAY
or
50N-3 DELAY
,
50N-2
DELAY
continues running in the meantime. After the dropout delay time has elapsed, the pickup is reported
OFF and the trip delay time is reset unless the threshold
50-3 PICKUP
,
50-2 PICKUP
or
50N-3 PICKUP
,
50N-2 PICKUP
has been exceeded again. If the threshold is exceeded again during the dropout delay time,
the time is cancelled. The trip delay time
50-3 DELAY
,
50-2 DELAY
or
50N-3 DELAY
,
50N-2 DELAY
con-
tinues running in the meantime. If the threshold value is exceeded after its expiry, the trip command is issued
immediately. If the threshold value is not exceeded at this time, there is no reaction. If the threshold value is
exceeded again after expiry of the trip-command delay time, while the dropout delay time is still running, trip-
ping occurs immediately.
These elements can be blocked by the automatic reclosing feature (79 AR).
The following figures give an example of logic diagrams for the high-set elements
50-2 PICKUP
or
50N-2 PICKUP
. They also apply analogously to the high-set elements
50-3 PICKUP
and
50N-3 PICKUP
.
Overcurrent Ele-
ments
Connection to
Automatic Reclosing
Manual
CLOSE
Dynamic
Cold Load Pickup
Inrush Restraint
50-1
•
•
•
•
50-2
•
•
•
50-3
•
•
•
51
•
•
•
•
50N-1
•
•
•
•
50N-2
•
•
•
50N-3
•
•
•
51N
•
•
•
•