9016
RTD 1 STAGE 2
RTD-Box
-58 .. 482 °F;
∞
248 °F
RTD 1: Temperature Stage 2
Pickup
9021A
RTD 2 TYPE
RTD-Box
Not connected
Pt 100
Ω
Ni 120
Ω
Ni 100
Ω
Not connected
RTD 2: Type
9022A
RTD 2 LOCATION
RTD-Box
Oil
Ambient
Winding
Bearing
Other
Other
RTD 2: Location
9023
RTD 2 STAGE 1
RTD-Box
-50 .. 250 °C;
∞
100 °C
RTD 2: Temperature Stage 1
Pickup
9024
RTD 2 STAGE 1
RTD-Box
-58 .. 482 °F;
∞
212 °F
RTD 2: Temperature Stage 1
Pickup
9025
RTD 2 STAGE 2
RTD-Box
-50 .. 250 °C;
∞
120 °C
RTD 2: Temperature Stage 2
Pickup
9026
RTD 2 STAGE 2
RTD-Box
-58 .. 482 °F;
∞
248 °F
RTD 2: Temperature Stage 2
Pickup
9031A
RTD 3 TYPE
RTD-Box
Not connected
Pt 100
Ω
Ni 120
Ω
Ni 100
Ω
Not connected
RTD 3: Type
9032A
RTD 3 LOCATION
RTD-Box
Oil
Ambient
Winding
Bearing
Other
Other
RTD 3: Location
9033
RTD 3 STAGE 1
RTD-Box
-50 .. 250 °C;
∞
100 °C
RTD 3: Temperature Stage 1
Pickup
9034
RTD 3 STAGE 1
RTD-Box
-58 .. 482 °F;
∞
212 °F
RTD 3: Temperature Stage 1
Pickup
9035
RTD 3 STAGE 2
RTD-Box
-50 .. 250 °C;
∞
120 °C
RTD 3: Temperature Stage 2
Pickup
9036
RTD 3 STAGE 2
RTD-Box
-58 .. 482 °F;
∞
248 °F
RTD 3: Temperature Stage 2
Pickup
9041A
RTD 4 TYPE
RTD-Box
Not connected
Pt 100
Ω
Ni 120
Ω
Ni 100
Ω
Not connected
RTD 4: Type
9042A
RTD 4 LOCATION
RTD-Box
Oil
Ambient
Winding
Bearing
Other
Other
RTD 4: Location
9043
RTD 4 STAGE 1
RTD-Box
-50 .. 250 °C;
∞
100 °C
RTD 4: Temperature Stage 1
Pickup
9044
RTD 4 STAGE 1
RTD-Box
-58 .. 482 °F;
∞
212 °F
RTD 4: Temperature Stage 1
Pickup
9045
RTD 4 STAGE 2
RTD-Box
-50 .. 250 °C;
∞
120 °C
RTD 4: Temperature Stage 2
Pickup
9046
RTD 4 STAGE 2
RTD-Box
-58 .. 482 °F;
∞
248 °F
RTD 4: Temperature Stage 2
Pickup
9051A
RTD 5 TYPE
RTD-Box
Not connected
Pt 100
Ω
Ni 120
Ω
Ni 100
Ω
Not connected
RTD 5: Type
9052A
RTD 5 LOCATION
RTD-Box
Oil
Ambient
Winding
Bearing
Other
Other
RTD 5: Location
9053
RTD 5 STAGE 1
RTD-Box
-50 .. 250 °C;
∞
100 °C
RTD 5: Temperature Stage 1
Pickup
9054
RTD 5 STAGE 1
RTD-Box
-58 .. 482 °F;
∞
212 °F
RTD 5: Temperature Stage 1
Pickup
9055
RTD 5 STAGE 2
RTD-Box
-50 .. 250 °C;
∞
120 °C
RTD 5: Temperature Stage 2
Pickup