2.14 Backup Time Overcurrent Protection
273
7SD5 Manual
C53000-G1176-C169-1
The
I
>>> stage can, however, also be used as a standard additional and independent
overcurrent stage, since it works independent of the other stages. In this case, the
enable input
„>I-STUB ENABLE“
must be activated permanently (via a binary input
or CFC).
Figure 2-119
Logic diagram of the
I
>>> stage
Instantaneous Trip-
ping before Auto-
matic Reclosure
Automatic reclosure is applied in order to instantaneously remove the fault before au-
tomatic reclosure. A release signal from an external automatic reclosure device can
be injected via binary input
„>O/C InstTRIP“
. The internal automatic reclosure - if
available - is also effected by this command. Any stage of the overcurrent protection
can thus perform an instantaneous trip before reclosure via the parameter
Telep/BI
...
.
www
. ElectricalPartManuals
. com
Содержание siprotec 7SD5
Страница 2: ...2 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 4: ...4 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 18: ...Contents 18 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 34: ...1 Introduction 34 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 444: ...2 Functions 444 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 580: ...4 Technical Data 580 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 682: ...Literature 682 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 698: ...Index 698 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...