2 Functions
294
7SD5 Manual
C53000-G1176-C169-1
tion 2.11) or the reception of a remote trip (Section 2.12) since theses signals are
passed through the tripping logic of the entire device.
But when the device issues a single-pole trip command while an external single-pole
trip signal reaches the device via one of the binary inputs, e.g.
„>Trip L1 AR“
, then
this is not routed to the tripping logic, but only to the auto-reclosure function. In this
case, three-pole trip is ensured only if the forced three-pole trip is effective.
The forced three-pole coupling is also activated when only three-pole cycles are al-
lowed, but a single-pole trip is signalled externally via a binary input.
Dead Line Check
(DLC)
If the voltage of a disconnected phase does not disappear following a trip, reclosure
can be prevented. A prerequisite for this function is that the voltage transformers are
connected on the line side of the circuit breaker. To select this function the dead line
check must be activated. The automatic reclosure function then checks the discon-
nected line for no-voltage: the line must have been without voltage for at least an ad-
equate measuring time during the dead time. If this was not the case, the reclosure is
blocked dynamically.
This no-voltage check on the line is of advantage if a small generator (e.g. wind gen-
erator) is connected along the line.
Adaptive Dead
Time (ADT)
In all the previous alternatives it was assumed that defined and equal dead times were
set at both line ends, if necessary for different fault types and/or reclose cycles.
It is also possible to set the dead times (if necessary different for various fault types
and/or reclose cycles) at one line end only and to configure the adaptive dead time at
the other end (or ends). This can be done provided that the voltage transformers are
located on the line side of the circuit breaker or that facilities for transfer of a close
command to the remote line end exists.
Figure 2-123 shows an example with voltage measurement. It is assumed that the
device I is operating with defined dead times whereas the adaptive dead time is con-
figured at position II. It is important that the line is at least fed from busbar A, i.e. the
side with the defined dead times.
With the adaptive dead time the automatic reclosure function at line end II decides in-
dependently if and when reclosure is sensible and allowed and when it is not. The cri-
terion is the line voltage at end II, which was re-applied from end I following reclosure
there. Reclosure therefore takes place at end II as soon as it is apparent that voltage
has been re-applied to the line from end I.
In the illustrated example, the lines are disconnected at positions I, II and III. At I re-
closure takes place after the parameterized dead time. At III a reduced dead time can
take place (see above) if there is also an infeed on busbar B.
If the fault has been cleared (successful reclosure), line A - B is re-connected to the
voltage at busbar A through position I. Device II detects this voltage and also recloses
after a short delay (to ensure a sufficient voltage measuring time). The fault is cleared.
If the fault has not been cleared after reclosure at I (unsuccessful reclosure), a switch
on to fault occurs at I, no healthy voltage appears at II. The device there detects this
and does not reclose.
In the case of multiple reclosure the sequence may be repeated several times follow-
ing an unsuccessful reclosure until one of the reclosures attempts is successful or a
final trip takes place.
www
. ElectricalPartManuals
. com
Содержание siprotec 7SD5
Страница 2: ...2 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 4: ...4 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 18: ...Contents 18 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 34: ...1 Introduction 34 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 444: ...2 Functions 444 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 580: ...4 Technical Data 580 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 682: ...Literature 682 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 698: ...Index 698 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...