2 Functions
424
7SD5 Manual
C53000-G1176-C169-1
Table 2-20
Operational measured values of the local device
1)
according to address 1104
2)
according to address 1103
3)
considering factor 221 I4/Iph CT
Measured Values
Primary
Second-
ary
% Referred to
I
L1
;
I
L2
;
I
L3
Phase currents
A
A
I
EE
Sensitive earth current
A
mA
Nominal operational current
3
I
0
Earth current
A
A
ϕ
(
I
L1
-I
L2
),
ϕ
(
I
L2
-
I
L3
),
ϕ
(
I
L3
-
I
L1
)
Phase angle of the phase currents
towards each other
°
–
–
I
1
,
I
2
Positive and negative sequence com-
ponent of currents
A
A
I
Y
,
I
P
Transformer starpoint current or earth
current of the parallel line
A
A
Nominal operational current
U
L1-L2
, U
L2-L3
, U
L3-L1
Phase-to-phase voltages
kV
V
Nominal operational voltage
U
L1-E
, U
L2-E
, U
L3-E
Phase-earth voltage
kV
V
Nominal operational voltage /
√
3
3U
0
; U
0
Displacement voltage
kV
V
Nominal operational voltage /
√
3
ϕ
(U
L1
-U
L2
),
ϕ
(U
L2
-U
L3
),
ϕ
(U
L3
-U
L1
)
Phase angle of the phase voltages
towards each other
°
–
–
ϕ
(U
L1
-
I
L1
),
ϕ
(U
L2
-
I
L2
),
ϕ
(U
L3
-
I
L3
)
Phase angle of the phase voltages
towards the phase currents
°
–
–
U
1
, U
2
Positive and negative sequence com-
ponent of the voltages
kV
V
Nominal operational voltage /
√
3
U
X
; U
EN
Voltage at measuring input U
4
–
V
–
U
1compound
Positive sequence component of volt-
ages at the remote end (if compound-
ing is active in voltage protection)
kV
V
Operational rated voltage /
√
R
L1-E
, R
L2-E
,
R
L3-E
, R
L1-L2
,
R
L1-L2
, R
L3-L1
,
Operational resistance of all loops
Ω
Ω
–
X
L1-E
, X
L2-E
,
X
L3-E
, X
L1-L2
,
X
L2-L3
, X
L3-L1
,
Operational reactance of all loops
Ω
Ω
–
S, P, Q
Apparent, active and reactive power
MVA,
MW,
MVAR
–
√
3·U
N
·
I
N
Nominal operational
quantities
cos
ϕ
Power factor
(abs)
(abs)
–
f
Frequency (constellation frequency)
Hz
Hz
Nominal frequency
Θ
L1
/
Θ
TRIP
,
Θ
L2
/
Θ
TRIP
,
Θ
L3
/
Θ
TRIP
Thermal value of each phase,
referred to the tripping value
%
–
Trip overtemperature
Θ
/
Θ
TRIP
Resulting thermal value,
referred to the tripping value, calculat-
ed according to the set method
%
–
Trip overtemperature
U
Line
, U
Bus
, U
Diff
Line voltage, busbar voltage and
voltage difference (for synchronism
check)
kV
–
–
f
Line
, f
Bus
, f
Diff
Line voltage, busbar frequency and
voltage difference (for synchronism
check)
Hz
–
–
ϕ
Diff
Amount of phase angle difference
between line and busbar (for synchro-
nism check)
°
–
–
www
. ElectricalPartManuals
. com
Содержание siprotec 7SD5
Страница 2: ...2 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 4: ...4 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 18: ...Contents 18 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 34: ...1 Introduction 34 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 444: ...2 Functions 444 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 580: ...4 Technical Data 580 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 682: ...Literature 682 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 698: ...Index 698 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...