3.1 Mounting and Connections
461
7SD5 Manual
C53000-G1176-C169-1
The set nominal current of the current input transformers are checked on the input/out-
put board C-I/O-2. All jumpers must be set for one nominal current, i.e. one jumper
(X61 to X64) for each input transformer and additionally the common jumper X60.
But
:
In the version with sensitive earth fault current input (input transformer T8) there is no
jumper X64.
Jumpers X71, X72 and X73 on the input/output board C-I/O-2 are used to set the bus
address and must not be changed. The following table lists the jumper presettings.
Mounting location:
with housing size
1
/
2
: No. 3 in Figure 3-3, slot 33,
with housing size
1
/
1
: No. 3 in Figure 3-4, slot 33 right.
Table 3-9
Jumper settings of
Board Address
of the input/output board C-I/O-2
Jumper
Factory Setting
X71
1-2 (H)
X72
1-2 (H)
X73
2-3 (L)
www
. ElectricalPartManuals
. com
Содержание siprotec 7SD5
Страница 2: ...2 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 4: ...4 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 18: ...Contents 18 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 34: ...1 Introduction 34 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 444: ...2 Functions 444 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 580: ...4 Technical Data 580 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 682: ...Literature 682 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 698: ...Index 698 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...