2.15 Automatic Reclosure Function (optional)
311
7SD5 Manual
C53000-G1176-C169-1
3461
2.AR: START
YES
NO
NO
AR start allowed in this cycle
3462
2.AR: T-ACTION
0.01 .. 300.00 sec;
∞
0.20 sec
Action time
3464
2.AR Tdead 1Flt
0.01 .. 1800.00 sec;
∞
1.20 sec
Dead time after 1phase faults
3465
2.AR Tdead 2Flt
0.01 .. 1800.00 sec;
∞
1.20 sec
Dead time after 2phase faults
3466
2.AR Tdead 3Flt
0.01 .. 1800.00 sec;
∞
0.50 sec
Dead time after 3phase faults
3467
2.AR Tdead1Trip
0.01 .. 1800.00 sec;
∞
∞
sec
Dead time after 1pole trip
3468
2.AR Tdead3Trip
0.01 .. 1800.00 sec;
∞
0.50 sec
Dead time after 3pole trip
3469
2.AR: Tdead EV.
0.01 .. 1800.00 sec
1.20 sec
Dead time after evolving fault
3470
2.AR: CB? CLOSE
YES
NO
NO
CB ready interrogation before re-
closing
3471
2.AR SynRequest
YES
NO
NO
Request for synchro-check after
3pole AR
3472
3.AR: START
YES
NO
NO
AR start allowed in this cycle
3473
3.AR: T-ACTION
0.01 .. 300.00 sec;
∞
0.20 sec
Action time
3475
3.AR Tdead 1Flt
0.01 .. 1800.00 sec;
∞
1.20 sec
Dead time after 1phase faults
3476
3.AR Tdead 2Flt
0.01 .. 1800.00 sec;
∞
1.20 sec
Dead time after 2phase faults
3477
3.AR Tdead 3Flt
0.01 .. 1800.00 sec;
∞
0.50 sec
Dead time after 3phase faults
3478
3.AR Tdead1Trip
0.01 .. 1800.00 sec;
∞
∞
sec
Dead time after 1pole trip
3479
3.AR Tdead3Trip
0.01 .. 1800.00 sec;
∞
0.50 sec
Dead time after 3pole trip
3480
3.AR: Tdead EV.
0.01 .. 1800.00 sec
1.20 sec
Dead time after evolving fault
3481
3.AR: CB? CLOSE
YES
NO
NO
CB ready interrogation before re-
closing
3482
3.AR SynRequest
YES
NO
NO
Request for synchro-check after
3pole AR
3483
4.AR: START
YES
NO
NO
AR start allowed in this cycle
3484
4.AR: T-ACTION
0.01 .. 300.00 sec;
∞
0.20 sec
Action time
3486
4.AR Tdead 1Flt
0.01 .. 1800.00 sec;
∞
1.20 sec
Dead time after 1phase faults
3487
4.AR Tdead 2Flt
0.01 .. 1800.00 sec;
∞
1.20 sec
Dead time after 2phase faults
3488
4.AR Tdead 3Flt
0.01 .. 1800.00 sec;
∞
0.50 sec
Dead time after 3phase faults
3489
4.AR Tdead1Trip
0.01 .. 1800.00 sec;
∞
∞
sec
Dead time after 1pole trip
3490
4.AR Tdead3Trip
0.01 .. 1800.00 sec;
∞
0.50 sec
Dead time after 3pole trip
3491
4.AR: Tdead EV.
0.01 .. 1800.00 sec
1.20 sec
Dead time after evolving fault
3492
4.AR: CB? CLOSE
YES
NO
NO
CB ready interrogation before re-
closing
3493
4.AR SynRequest
YES
NO
NO
Request for synchro-check after
3pole AR
Addr.
Parameter
Setting Options
Default Setting
Comments
www
. ElectricalPartManuals
. com
Содержание siprotec 7SD5
Страница 2: ...2 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 4: ...4 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 18: ...Contents 18 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 34: ...1 Introduction 34 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 444: ...2 Functions 444 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 580: ...4 Technical Data 580 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 682: ...Literature 682 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 698: ...Index 698 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...