2 Functions
220
7SD5 Manual
C53000-G1176-C169-1
the earth fault protection for any fault type (any distance protection pickup) occurring
within zone Z1, the setting
3102
BLOCK for Dist.
=
every PICKUP
and
3174
BLK for DisZone
=
in zone Z1
applies.
The earth fault protection must be blocked during single-pole automatic reclose dead
time to avoid pick-up with the false zero sequence values and, if applicable, the neg-
ative sequence values arising during this state (address
3103
BLOCK 1pDeadTim
).
A setting of
YES
(default setting for devices with single-pole tripping) is required if
single-pole automatic reclosure is to be carried out. Otherwise set
NO
. Setting param-
eter
3103
BLOCK 1pDeadTim
to
YES
completely blocks the earth fault protection if
the Open-Pole Detector has recognized a single-pole dead time. If no single-pole trip-
ping is carried out in the protected network, it is absolutely necessary to set this pa-
rameter to
NO
.
Regardless of how parameter address
3103
BLOCK 1pDeadTim
is set, the earth fault
protection will always be blocked during the single-pole dead time, if it has issued a
trip command itself. This is necessary because otherwise the picked up earth fault pro-
tection cannot drop out if the fault current was caused by load current.
Trip
Address
3109
Trip 1pole E/F
specifies that the earth fault protection trips single
pole, provided that the faulted phase can be determined with certainty. This address
is only valid for devices that have the option to trip single-pole. If you are using single-
pole automatic reclosure, the setting
YES
(default setting) remains valid. Otherwise set
NO
.
Definite Time
Stages
First of all, the mode for each stage is set: address
3110
Op. mode 3I0>>>
, address
3120
Op. mode 3I0>>
and address
3130
Op. mode 3I0>
. Each stage can be set
to operate
Forward
(usually towards line),
Reverse
(usually towards busbar) or
Non-Directional
(in both directions). If a single stage is not required, set its mode
to
Inactive
.
The definite time stages
3I0>>>
(address
3111
),
3I0>>
(address
3121
) and
3I0>
(address
3131
) can be used for a three-stage definite time overcurrent protection.
They can also be combined with the inverse time stage
3I0p PICKUP
(address
3141
,
see below). The pick up thresholds should in general be selected such that the most
sensitive stage picks up with the smallest expected earth fault current.
The 3
I
0
>> and 3
I
0
>>> stages are best suited for fast tripping stages (instantaneous),
as these stages use an abridged filter with shorter response time. On the other hand,
the stages 3
I
0
> and 3
I
0P
are best suited for very sensitive earth fault detection due to
their effective method of suppressing harmonics.
If no inverse time stage, but rather a fourth definite time stage is required, the „inverse
time“ stage can be implemented as a definite time stage. This must already be taken
regard of during the configuration of the protection functions (refer to Section 2.1.1.3,
address
131
Earth Fault O/C
=
Definite Time
). For this stage, the address
3141
3I0p PICKUP
then determines the current pickup threshold and address
3147
Add.T-DELAY
the definite time delay.
The values for the time delay settings
T 3I0>>>
(address
3112
),
T 3I0>>
(address
3122
) and
T 3I0>
(address
3132
) are derived from the earth fault grading coordina-
tion diagram of the system.
During the selection of the current and time settings, regard must be taken as to
whether a stage should be direction dependent and whether it uses teleprotection.
Refer also to the margin headings „Determination of Direction“ and „Teleprotection
with Earth Fault Protection“.
www
. ElectricalPartManuals
. com
Содержание siprotec 7SD5
Страница 2: ...2 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 4: ...4 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 18: ...Contents 18 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 34: ...1 Introduction 34 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 444: ...2 Functions 444 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 580: ...4 Technical Data 580 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 682: ...Literature 682 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 698: ...Index 698 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...