2.22 Monitoring Functions
395
7SD5 Manual
C53000-G1176-C169-1
2.22.2.2 Setting Notes
General
The number of circuits to be supervised was set during the configuration in address
140
Trip Cir. Sup.
(Section 2.1.1.3). If the trip circuit supervision is not used at
all, the setting
Disabled
must be applied there.
The trip circuit supervision can be switched
ON
or
OFF
in address
4001
FCT
TripSuperv.
. The number of binary inputs that shall be used in each of the super-
vised circuits is set in address
4002
No. of BI
. If the routing of the binary inputs
required for this does not comply with the selected supervision mode, an alarm is
given (
„TripC1 ProgFAIL ...“
, with identification of the non-compliant circuit).
Supervision with
One Binary Input
The alarm for supervision with two binary inputs is always delayed by approx. 1 s to
2 s, whereas the delay time of the alarm for supervision with one binary input can be
set in address
4003
Alarm Delay
. 1 s to 2 s are sufficient if only the 7SD5 device is
connected to the trip circuits as the trip circuit supervision does not operate during a
system fault. If, however, trip contacts from other devices are connected in parallel in
the trip circuit, the alarm must be delayed such that the longest trip command duration
can be reliably bridged.
2.22.2.3 Settings
2.22.2.4 Information List
Addr.
Parameter
Setting Options
Default Setting
Comments
4001
FCT TripSuperv.
ON
OFF
OFF
TRIP Circuit Supervision is
4002
No. of BI
1 .. 2
2
Number of Binary Inputs per trip
circuit
4003
Alarm Delay
1 .. 30 sec
2 sec
Delay Time for alarm
No.
Information
Type of In-
formation
Comments
6854
>TripC1 TripRel
SP
>Trip circuit superv. 1: Trip Relay
6855
>TripC1 Bkr.Rel
SP
>Trip circuit superv. 1: Breaker Relay
6856
>TripC2 TripRel
SP
>Trip circuit superv. 2: Trip Relay
6857
>TripC2 Bkr.Rel
SP
>Trip circuit superv. 2: Breaker Relay
6858
>TripC3 TripRel
SP
>Trip circuit superv. 3: Trip Relay
6859
>TripC3 Bkr.Rel
SP
>Trip circuit superv. 3: Breaker Relay
6861
TripC OFF
OUT
Trip circuit supervision OFF
6865
FAIL: Trip cir.
OUT
Failure Trip Circuit
6866
TripC1 ProgFAIL
OUT
TripC1 blocked: Binary input is not set
6867
TripC2 ProgFAIL
OUT
TripC2 blocked: Binary input is not set
6868
TripC3 ProgFAIL
OUT
TripC3 blocked: Binary input is not set
www
. ElectricalPartManuals
. com
Содержание siprotec 7SD5
Страница 2: ...2 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 4: ...4 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 18: ...Contents 18 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 34: ...1 Introduction 34 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 444: ...2 Functions 444 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 580: ...4 Technical Data 580 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 682: ...Literature 682 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 698: ...Index 698 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...