2.8 Earth Fault Protection in Earthed Systems (optional)
227
7SD5 Manual
C53000-G1176-C169-1
3IoMin Teleprot
(address
3105
) must be set to avoid non-selective tripping during
through-fault earth current measurement. For further information refer to Section 2.9,
margin heading „Earth Fault Protection Prerequisites“.
Switching onto an
Earth Fault
It is possible to determine with a setting which stage trips without delay following
closure onto a dead fault. The parameters
3I0>>>SOTF-Trip
(address
3114
),
3I0>> SOTF-Trip
(address
3124
),
3I0> SOTF-Trip
(address
3134
) and, if nec-
essary,
3I0p SOTF-Trip
(address
3149
) are available for the stages which can be
set to
YES
or
NO
for each stage. Selection of the most sensitive stage is usually not
reasonable as a solid short-circuit may be assumed following switching onto a fault,
whereas the most sensitive stage often also has to detect high resistance faults. It is
important to avoid that the selected stage picks up in a transient way during line ener-
gization.
On the other hand, it does not matter if a selected stage may pick up due to inrush
conditions on transformers. The switch-onto-fault tripping of a stage is blocked by the
inrush restraint even if it is set as instantaneous switch-onto-fault stage for manual clo-
sure.
To avoid a spurious pickup due to transient overcurrents, the delay
SOTF Time
DELAY
(address
3173
) can be set. Usually, the default setting
0
can be retained. In
the case of long cables, where large peak inrush currents can occur, a short delay may
be useful. The time delay depends on the severity and duration of the transient over-
currents as well as on which stages were selected for the fast switch onto fault clear-
ance.
With the parameter
SOTF Op. Mode
(address
3172
) it is finally possible to determine
whether the fault direction must be checked (
DIRECT.
) or not (
PICKUP
),
before a switch-onto-fault tripping is generated. It is the direction setting for each stage
that applies for this direction check.
Phase Current Re-
straint
To avoid a spurious pickup of the stages in the case of asymmetrical load conditions
or varying current transformer measuring errors in earth systems, the earth current
stages are restrained by the phase currents: as the phase currents increase, the
pickup thresholds are increased. By means of the setting in address
3104
Iph-
STAB. Slope
the preset value of 10 % for all stages can be jointly changed for all
stages. This setting is only possible via DIGSI
®
at
Additional Settings
.
Inrush Restraint
The inrush restraint is only required if the device is applied to transformer feeders or
on lines that end on a transformer; in this case also only for such stages that have a
pickup threshold below the inrush current and have a very short or zero delay. The pa-
rameters
3I0>>>InrushBlk
(address
3115
),
3I0>> InrushBlk
(address
3125
),
3I0> InrushBlk
(address
3135
) and
3I0p InrushBlk
(address
3150
) can be
set to
YES
(inrush restraint active) or
NO
(inrush restraint inactive) for each stage. If the
inrush restraint has been disabled for all stages, the following parameters are of no
consequence.
For the recognition of the inrush current, the portion of second harmonic current
content referred to the fundamental current component can be set in address
3170
2nd InrushRest
. Above this threshold the inrush blocking is effective. The preset
value (15 %) should be sufficient in most cases. Lower values imply higher sensitivity
of the inrush blocking (smaller portion of second harmonic current results in blocking).
In applications on transformer feeders or lines that are terminated on transformers it
may be assumed that, if very large currents occur, a short-circuit has occurred in front
of the transformer. In the event of such large currents, the inrush restraint is inhibited.
www
. ElectricalPartManuals
. com
Содержание siprotec 7SD5
Страница 2: ...2 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 4: ...4 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 18: ...Contents 18 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 34: ...1 Introduction 34 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 444: ...2 Functions 444 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 580: ...4 Technical Data 580 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 682: ...Literature 682 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 698: ...Index 698 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...