2.22 Monitoring Functions
391
7SD5 Manual
C53000-G1176-C169-1
2.22.1.7 Information List
2.22.2 Trip Circuit Supervision
The line protection 7SD5 is equipped with an integrated trip circuit supervision func-
tion. Depending on the number of available binary inputs (not connected to a common
potential), supervision with one or two binary inputs can be selected. If the routing of
the binary inputs required for this does not comply with the selected supervision mode,
an alarm is given („TripC1 ProgFAIL ...“, with identification of the non-compliant cir-
cuit). When using two binary inputs, malfunctions in the trip circuit can be detected
under all circuit breaker conditions. When only one binary input is used, malfunctions
in the circuit breaker itself cannot be detected. If single-pole tripping is possible, a sep-
arate trip circuit supervision can be implemented for each circuit breaker pole provided
the required binary inputs are available.
2915
V-Supervision
w/ CURR.SUP
w/ I> & CBaux
OFF
w/ CURR.SUP
Voltage Failure Supervi-
sion
2916A
T V-Supervision
0.00 .. 30.00 sec
3.00 sec
Delay Voltage Failure Su-
pervision
2921
T mcb
0 .. 30 ms
0 ms
VT mcb operating time
2931
BROKEN WIRE
ON
OFF
OFF
Fast broken current-wire
supervision
2933
FAST
Σ
i SUPERV
ON
OFF
ON
State of fast current sum-
mation supervis
No.
Information
Type of In-
formation
Comments
161
Fail I Superv.
OUT
Failure: General Current Supervision
163
Fail I balance
OUT
Failure: Current Balance
164
Fail U Superv.
OUT
Failure: General Voltage Supervision
165
Fail
Σ
U Ph-E
OUT
Failure: Voltage summation Phase-Earth
167
Fail U balance
OUT
Failure: Voltage Balance
168
Fail U absent
OUT
Failure: Voltage absent
169
VT FuseFail>10s
OUT
VT Fuse Failure (alarm >10s)
170
VT FuseFail
OUT
VT Fuse Failure (alarm instantaneous)
171
Fail Ph. Seq.
OUT
Failure: Phase Sequence
196
Fuse Fail M.OFF
OUT
Fuse Fail Monitor is switched OFF
197
MeasSup OFF
OUT
Measurement Supervision is switched OFF
289
Failure
Σ
i
OUT
Alarm: Current summation supervision
290
Broken Iwire L1
OUT
Alarm: Broken current-wire detected L1
291
Broken Iwire L2
OUT
Alarm: Broken current-wire detected L2
292
Broken Iwire L3
OUT
Alarm: Broken current-wire detected L3
295
Broken wire OFF
OUT
Broken wire supervision is switched OFF
296
Σ
i superv. OFF
OUT
Current summation superv is switched OFF
Addr.
Parameter
C
Setting Options
Default Setting
Comments
www
. ElectricalPartManuals
. com
Содержание siprotec 7SD5
Страница 2: ...2 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 4: ...4 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 18: ...Contents 18 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 34: ...1 Introduction 34 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 444: ...2 Functions 444 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 580: ...4 Technical Data 580 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 682: ...Literature 682 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 698: ...Index 698 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...