2 Functions
112
7SD5 Manual
C53000-G1176-C169-1
The earth fault recognition alone does not cause a general pickup of the distance pro-
tection, but merely controls the further fault detection modules. It is only alarmed in
case of a general fault detection.
Figure 2-29
Logic of the earth fault detection
Earth Fault Recog-
nition during
Single-Pole Open
Condition
In order to prevent undesired pickup of the earth fault detection, caused by load cur-
rents during single-pole open condition, a modified earth fault detection is used during
single-pole open condition in earthed power systems (Figure 2-30). In this case, the
magnitudes of the currents and voltages are monitored in addition to the angles
between the currents.
Figure 2-30
Earth fault recognition during single-pole open condition
Logical Combina-
tion for Non-
earthed Systems
In non-earthed systems (isolated system starpoint or resonant-earthed by means of a
Peterson coil) the measured displacement voltage is not used for fault detection. Fur-
thermore, in these systems a simple earth fault is assumed initially in case of a single-
phase fault and the fault detection is suppressed in order to avoid an erroneous pickup
as a result of the earth fault initiation transients. After a time delay
T3I0 1PHAS
which
can be set, the fault detection is released again; this is necessary for the distance pro-
tection to still be able to detect a double earth fault with one base point on a dead-end
feeder.
If, however, an earth fault is already present in the system, it is detected by the dis-
placement voltage detection (
3U0> COMP/ISOL.
). In this case, there is no delay
time: an earth fault occurring now in a different phase can only be a double earth fault.
www
. ElectricalPartManuals
. com
Содержание siprotec 7SD5
Страница 2: ...2 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 4: ...4 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 18: ...Contents 18 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 34: ...1 Introduction 34 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 444: ...2 Functions 444 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 580: ...4 Technical Data 580 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 682: ...Literature 682 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 698: ...Index 698 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...