2 Functions
346
7SD5 Manual
C53000-G1176-C169-1
Further application examples exist in the field of power stations. The frequency values
to be set mainly depend, also in these cases, on the specifications of the power sys-
tem/power station operator. In this context, the underfrequency protection also
ensures the power station’s own demand by disconnecting it from the power system
on time. The turbo regulator regulates the machine set to the nominal speed. Conse-
quently, the station's own demands can be continuously supplied at nominal frequen-
cy.
Since the dropout threshold is 20 mHz below or above the trip frequency, the resulting
„minimum“ trip frequency is 30 mHz above or below the nominal frequency.
A frequency increase can, for example, occur due to a load shedding or malfunction
of the speed regulation (e.g. in a stand-alone system). In this way, the frequency pro-
tection can, for example, be used as overspeed protection.
2.18.3 Settings
Addr.
Parameter
Setting Options
Default Setting
Comments
3601
O/U FREQ. f1
ON: Alarm only
ON: with Trip
OFF
ON: Alarm only
Over/Under Frequency Protection
stage f1
3602
f1 PICKUP
45.50 .. 54.50 Hz
49.50 Hz
f1 Pickup
3603
f1 PICKUP
55.50 .. 64.50 Hz
59.50 Hz
f1 Pickup
3604
T f1
0.00 .. 600.00 sec
60.00 sec
T f1 Time Delay
3611
O/U FREQ. f2
ON: Alarm only
ON: with Trip
OFF
ON: Alarm only
Over/Under Frequency Protection
stage f2
3612
f2 PICKUP
45.50 .. 54.50 Hz
49.00 Hz
f2 Pickup
3613
f2 PICKUP
55.50 .. 64.50 Hz
57.00 Hz
f2 Pickup
3614
T f2
0.00 .. 600.00 sec
30.00 sec
T f2 Time Delay
3621
O/U FREQ. f3
ON: Alarm only
ON: with Trip
OFF
ON: Alarm only
Over/Under Frequency Protection
stage f3
3622
f3 PICKUP
45.50 .. 54.50 Hz
47.50 Hz
f3 Pickup
3623
f3 PICKUP
55.50 .. 64.50 Hz
59.50 Hz
f3 Pickup
3624
T f3
0.00 .. 600.00 sec
3.00 sec
T f3 Time Delay
3631
O/U FREQ. f4
ON: Alarm only
ON: with Trip
OFF
ON: Alarm only
Over/Under Frequency Protection
stage f4
3632
f4 PICKUP
45.50 .. 54.50 Hz
51.00 Hz
f4 Pickup
3633
f4 PICKUP
55.50 .. 64.50 Hz
62.00 Hz
f4 Pickup
3634
T f4
0.00 .. 600.00 sec
30.00 sec
T f4 Time Delay
www
. ElectricalPartManuals
. com
Содержание siprotec 7SD5
Страница 2: ...2 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 4: ...4 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 18: ...Contents 18 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 34: ...1 Introduction 34 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 444: ...2 Functions 444 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 580: ...4 Technical Data 580 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 682: ...Literature 682 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 698: ...Index 698 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...