2 Functions
344
7SD5 Manual
C53000-G1176-C169-1
Figure 2-139
Logic diagram of the frequency protection
2.18.2 Setting Notes
General
Frequency protection is only in effect and accessible if address
136
FREQUENCY
Prot.
is set to
Enabled
during configuration of protective functions. If the function is
not required,
Disabled
is to be set.
The frequency protection function features 4 frequency stages f1 to f4 each of which
can function as overfrequency stage or underfrequency stage. Each zone can be set
active or inactive. This is set in addresses:
•
3601
O/U FREQ. f1
for frequency stage f1,
•
3611
O/U FREQ. f2
for frequency stage f2,
•
3621
O/U FREQ. f3
for frequency stage f3,
•
3631
O/U FREQ. f4
for frequency stage f4,
www
. ElectricalPartManuals
. com
Содержание siprotec 7SD5
Страница 2: ...2 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 4: ...4 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 18: ...Contents 18 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 34: ...1 Introduction 34 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 444: ...2 Functions 444 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 580: ...4 Technical Data 580 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 682: ...Literature 682 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 698: ...Index 698 7SD5 Manual C53000 G1176 C169 1 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...