SIMODRIVE alarms
11/2006
Overview of Alarms
2-689
©
Siemens AG, 2006. All rights reserved
SINUMERIK, SIMODRIVE Diagnostics Manual (DA), 11/2006 Edition
300003
Axis %1 drive %2 wrong module type %3
Parameters:
%1 = NC axis number
%2 = Drive number
%3 = Incorrect module type
Definitions:
The hardware configuration of the drive components established at the time of bus initialization does
not correspond to the information in machine data 13030 DRIVE_MODULE_TYPE[p]=... (p ... rack
location index).
Reaction:
NC not ready.
The NC switches to follow-up mode.
Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy:
Please inform the authorized personnel/service department. Enter MD 13030
DRIVE_MODULE_TYPE to match the drive modules that are plugged in.
Select MD 13010 DRIVE_LOGIC_NR and search for the drive logic number that is indicated in the
alarm text. The location index 1 results in the associated rack location number. The VDD
module belonging to this location is determined by the configuration in MD 13030
DRIVE_MODULE_TYPE for the same location index.
Input value 1: 1-axis module, input value 2: 2-axis module.
Program
Continuation:
Switch control OFF - ON.
300004
Axis %1 drive %2 wrong drive type %3 (FDD/MSD)
Parameters:
%1 = NC axis number
%2 = Drive number
%3 = Drive type code
Definitions:
A feed module is inserted in the rack location determined by the drive logic number, but in the
corresponding NCK-specific MD 13040 DRIVE_TYPE, a main spindle is defined (or vice versa).
Reaction:
NC not ready.
The NC switches to follow-up mode.
Channel not ready.
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy:
Please inform the authorized personnel/service department.
Select MD 13010 DRIVE_LOGIC_NR and search for the drive logic number that is indicated in the
alarm text. The location index 1 results in the associated rack location number. The
FDD/MSD module belonging to this location is determined by the configuration in MD 13040
DRIVE_TYPE for the same location index.
FDD: identifier 1, MSD: identifier 2.
Program
Continuation:
Switch control OFF - ON.