NCK alarms
11/2006
Overview of Alarms
2-301
©
Siemens AG, 2006. All rights reserved
SINUMERIK, SIMODRIVE Diagnostics Manual (DA), 11/2006 Edition
16773
Channel %1 axis %2 is the following axis. The axis/spindle disables of
leading axes %3 and %4 differ from one another.
Parameters:
%1 = Channel number
%2 = Axis, spindle
%3 = Axis, spindle
%4 = Axis, spindle
Definitions:
The axis is active in a coupling as a following axis. The master axes
have different states regarding axis/spindle disable.
The alarm can be suppressed with machine data 11415 SUPPRESS_ALARM_MASK_2 Bit0 =1.
Reaction:
Alarm display.
Remedy:
Set the same axis/spindle disable for all master axes.
Program
Continuation:
Alarm display showing cause of alarm disappears. No further operator action necessary.
16774
Channel %1 Synchronization aborted for slave axis/spindle %2
Parameters:
%1 = Channel number
%2 = Axis name, spindle number
Definitions:
For the indicated axis, the synchronization procedure (EGONSYN or EGONSYNE) was aborted.
There are several reasons for aborting the synchronization process:
- RESET
- End of program
- Axis goes to follow-up mode
- Rapid stop caused by an alarm
Reaction:
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Channel not ready.
Remedy:
If the abort of the synchronization procedure can be tolerated or is intended, the alarm can be
suppressed with machine data 11410 SUPPRESS_ALARM_MASK Bit31 = 1.
Only applicable for electronic gear (EG):
If it is not possible to abort the synchronization procedure, you can achieve it by specifying the block
change criterion FINE in EGONSYN or EGONSYNE.
Program
Continuation:
Clear alarm with the RESET key. Restart part program
16776
Channel %1 block %2 curve table %3 does not exist for axis %4
Parameters:
%1 = Channel number
%2 = Block number, label
%3 = Number of curve table
%4 = Axis name, spindle number
Definitions:
An attempt was made to couple axis %4 with curve table number %3, but no curve table of this number
exists.
Reaction:
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy:
Modify the NC part program so that the required curve table exists when axis link is to be activated.
Program
Continuation:
Clear alarm with the RESET key. Restart part program