0 to 20 and 4 to 20 mA operation. Some minor adjustment may be required for 0 to 10 VDC and
RTD usage due to application variations.
The board has a built in controller which manages the I/O peripherals and also the
communication between the board and the system. Software options exist to allow for the
choice of last state, defined state or zero state in case of loss of communications with the control.
The board itself requires an external power supply of 24 VDC. Two power supply connections are
provided to allow for a redundant power supply option. The board does not contain circuitry to
detect loss of power supply at this time. The connections to the system are simple and there are
removable plug-in terminal blocks for I/O and power supply. The fiber optics use the same
modular snap and lock system as the cells and bypass. Two ground lugs are provided for panel
bonding and shielding.
The following table shows the I/O identifiers and SOP flag names for each I/O point on the user
I/O boards connected via fiber optic interconnection:
I/O Type
I/O Name
Corresponding SOP Flags
Board 1 (Standard)
Analog input
AI1 to AI3
N/a
Analog output
AO1 to AO2
N/a
Digital input
DI1 (0a) to DI20 (3e)
InternalDigitalInput0a_I to InternalDigitalInput3e_I
Digital output
DO1 to DO16
InternalDigitalOutput0_O to InternalDigitalOutput15_O
Board 2 (Optional)
Analog input
AI4 to AI6
N/a
Analog output
AO3 to AO4
N/a
Digital input
DI21 (0a) to DI40 (3e)
InternalDigital2Input0a_I to InternalDigital2Input3e_I
Digital output
DO17 to DO32
InternalDigital2Output0_O to InternalDigital2Output15_O
Board 3 (Optional)
Analog input
AI7 to AI9
N/a
Analog output
AO5 to AO6
N/a
Digital input
DI41 (0a) to DI60 (3e)
InternalDigital3Input0a_I to InternalDigital3Input3e_I
Digital output
DO33 to DO48
InternalDigital3Output0_O to InternalDigital3Output15_O
Board 4 (Optional)
Analog input
AI10 to AI2
N/a
Analog output
AO7 to AO8
N/a
Digital input
DI61 (0a) to DI80 (3e)
InternalDigital4Input0a_I to InternalDigital4Input3e_I
Digital output
DO49 to DO64
InternalDigital4Output0_O to InternalDigital4Output15_O
5.3.6
Discrete External I/O via WAGO System
Note
WAGO support is for legacy products (Retrofits). For further information go to Siemens Technical
Support - www.siemens.com|automation|support-request.
Hardware User Interface Description
5.3 User Accessible Interfaces
Control Manual
74
Operating Manual, A5E50491925A
Содержание SINAMICS PERFECT HARMONY GH180
Страница 2: ......
Страница 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Страница 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Страница 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...
Страница 516: ...List of abbreviations C 1 Symbols and Abbreviations NXGPro Control Manual 514 Operating Manual A5E50491925A ...
Страница 517: ...Index D NXGPro Control Manual Operating Manual A5E50491925A 515 ...
Страница 518: ...Index NXGPro Control Manual 516 Operating Manual A5E50491925A ...
Страница 530: ...Glossary NXGPro Control Manual 528 Operating Manual A5E50491925A ...
Страница 537: ......
Страница 538: ... XUWKHU QIRUPDWLRQ ZZZ VLHPHQV FRP GULYHV 6LHPHQV QGXVWU QF 3 XQW 9DOOH 5RDG 1HZ HQVLQJWRQ 3 8QLWHG 6WDWHV RI PHULFD ...