This process magnifies offsets and noise that are introduced by the measurements. In order to
limit the gain at extremely low frequencies, the transfer function is approximated by 1/(s + a),
where a is the S/W compensator pole. The pole introduced by a affects the motor flux phase
angle, and is chosen to be low enough such that the error introduced is small.
In typical applications that have short cables between the motor and the VFD the default value of
a, 2 rad/s, provides a good compromise between flux phase angle error and reduced gain at dc.
In long cable applications, the effect of compensating the cable voltage drop, resistive and
inductive, causes additional terms to be introduced in the motor flux calculation, i.e. V
motor
= V
vfd
– I*R
cable
– I*w*L
cable
. This requires that a be increased so as to avoid the sensitivity of offsets and
measurement errors. However, there is an adverse effect on the starting torque capability.
Typically for cables longer than 5000 m, a can be set in the range of 4 to 6 rad/s. With such a
setting, enable High starting torque mode (2960) to maintain good starting torque capability.
Table 6-54
Flux Control Menu (3100) Parameters
Parameter
ID
Unit
Default
Min
Max
Description
Flux reg prop gain
3110
1.72
0.0
10.0
Flux PI regulator proportional gain term.
Flux reg integral
gain
3120
1.0
0.0
1200.0
Flux PI regulator integral gain term.
Flux filter time const 3130
sec
0.0667
0.0
10.0
Time constant of the low pass filter used on the
flux error.
Flux table menu
Note: To be re‐
leased in a later
software version.
3131
Submenu
Flux shaping table parameters
Flux demand
Note: To be re‐
leased in a later
software version.
3150
pu
1.0
0.16
10.0
Set the flux demand, or desired V/Hz ratio. Use the
default setting to set the V/Hz ratio to nameplate
values.
Flux ramp rate
Note: To be re‐
leased in a later
software version.
3160
sec
0.5
0.0
5.0
Set the ramp time to go from zero to rated flux.
This time establishes the time to magnetize the
motor.
Energy saver min
flux
3170
%
100.0
10.0
125.0
Set the lowest value of flux, as a percentage of
rated motor flux that the drive will apply to an
unloaded motor.
Energy Saver is enabled if you enter a value that is
less than the flux demand. The control establishes
the amount of flux or motor voltage that minimi‐
zes the losses in the motor.
Flux droop
3195
%
0
0
200
Set flux droop for parallel drives, to keep the volt‐
age balanced between drives. This parameter is
used for fine adjustments on flux droop with the
main reference coming from an external PLC. Re‐
fer to Section Parallel Drive Control for a single IM.
Parameter Assignment/Addressing
6.8 Options for Stability Menu (3) - first half
Control Manual
130
Operating Manual, A5E50491925A
Содержание SINAMICS PERFECT HARMONY GH180
Страница 2: ......
Страница 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Страница 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Страница 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...
Страница 516: ...List of abbreviations C 1 Symbols and Abbreviations NXGPro Control Manual 514 Operating Manual A5E50491925A ...
Страница 517: ...Index D NXGPro Control Manual Operating Manual A5E50491925A 515 ...
Страница 518: ...Index NXGPro Control Manual 516 Operating Manual A5E50491925A ...
Страница 530: ...Glossary NXGPro Control Manual 528 Operating Manual A5E50491925A ...
Страница 537: ......
Страница 538: ... XUWKHU QIRUPDWLRQ ZZZ VLHPHQV FRP GULYHV 6LHPHQV QGXVWU QF 3 XQW 9DOOH 5RDG 1HZ HQVLQJWRQ 3 8QLWHG 6WDWHV RI PHULFD ...