Fault display
Type
Enable
Potential causes and corrective actions
System Interface Conn
F
Fixed
Cause
The system has sense lines which indicate whether or not the cable to the
system interface board is attached. This cable attached to the system via
the fifty pin connector on the main control board. If this cable is not at‐
tached a "System Interface Conn" fault will be generated.
Action
1. Check that the cable to the system interface board is connected prop‐
erly.
2. Replace cable to system interface board.
3. Replace DCR.
4. Contact Siemens customer service.
Fiber Optic Board Conn
F
Fixed
Cause
The system has sense lines which indicate whether or not the fiber optic
board is installed. If the fiber optic board is not installed properly a "Fiber
Optic Board Conn" fault will be generated.
Action
1. Replace DCR.
2. Contact Siemens customer service.
FPGA CRC Error Fault
Note: This feature is not ap‐
plicable to control.
F
Fixed
Cause
The NXGpro’s main FPGA incorporates a CRC check system which detects
errors in the contained logic. This check system has an output which is fed
into the GLUE CPLD. The "FPGA CRC Error Fault" is generated when the CRC
error signal is received from the GLUE logic.
Action
1. Toggle control power.
2. Contact Siemens customer service.
F.O. Exp Bd Not found
F
Fixed
Cause
The system has sense lines which indicate whether or not each of the four
possible fiber optic expansion boards is installed. A "F.O. Exp Bd Not found"
fault will be generated if any the following conditions is satisfied:
1. The number of cells per phase parameter is greater than four and the
fiber optic expansion board for rank five is not installed.
2. The number of cells per phase parameter is greater than five and the
fiber optic expansion board for rank six is not installed.
3. The number of cells per phase parameter is greater than six and the
fiber optic expansion board for rank seven is not installed.
4. The number of cells per phase is equal to eight and the fiber optic
expansion board for rank eight is not installed.
Action
1. Check that the proper number of cells is entered in the system param‐
eter menus.
2. Replace DCR.
3. Contact Siemens customer service.
Troubleshooting Faults and Alarms
11.6 Drive Faults and Alarms System Related
Control Manual
456
Operating Manual, A5E50491925A
Содержание SINAMICS PERFECT HARMONY GH180
Страница 2: ......
Страница 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Страница 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Страница 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...
Страница 516: ...List of abbreviations C 1 Symbols and Abbreviations NXGPro Control Manual 514 Operating Manual A5E50491925A ...
Страница 517: ...Index D NXGPro Control Manual Operating Manual A5E50491925A 515 ...
Страница 518: ...Index NXGPro Control Manual 516 Operating Manual A5E50491925A ...
Страница 530: ...Glossary NXGPro Control Manual 528 Operating Manual A5E50491925A ...
Страница 537: ......
Страница 538: ... XUWKHU QIRUPDWLRQ ZZZ VLHPHQV FRP GULYHV 6LHPHQV QGXVWU QF 3 XQW 9DOOH 5RDG 1HZ HQVLQJWRQ 3 8QLWHG 6WDWHV RI PHULFD ...