controller. The external controller is a separate PLC for most applications and if the analog
control signal is a 4 to 20ma current loop.
NOTICE
Potential Circuitry Damage
4 to 20ma current loops cannot be switched without potentially damaging circuitry.
An intervening PLC can digitize the signals and retransmit the signal, facilitating the switching
function.
The PLC allows for monitoring and matching between an external field reference source and the
drive field reference source during transfer.
8.17.11
Synchronous Transfer Operation For Synchronous Motors Up Transfer (L29)
Up Transfer of Synchronous Motor
Up transfers are accomplished by taking the SM up to speed on the VFD to match the frequency
and then the phase of the line. This is accomplished the same as for an IM, by using the drive
input line frequency as a velocity reference. The main difference comes after the
synchronization and when both contactors are closed simultaneously. At this point the field
control has to be transferred from the drive to an external field controller. When the field transfer
is complete, the drive contactor is opened and the drive coast-stopped to end the transition.
8.17.12
Synchronous Transfer Operation For Synchronous Motors Down Transfer
Preconditions (L29)
Down Transfer of Synchronous Motor
Down transfer with synchronous motor control transfers a motor running directly connected to
a power line to the control via the VFD. The VFD output is synchronized with the line connected
to the motor, not necessarily the input to the drive. The control utilizes the connection through
the VFD output contactor with the power devices disabled to synchronize the VFD to the line.
Once synchronized, the outputs of the power devices are enabled in synchronization with the
line so that there is little or no power flow from the drive, and none back into the drive. A 2-
quadrant cannot absorb power.
Down transfer of synchronous motors not only involves the transfer of the stator voltage source
but also the transfer of the separate field exciter control. This adds a level of complexity to the
logic and control.
Down transfer of synchronous motors requires an external PLC or equivalent to control the
transfer and to provide the external field exciter reference when the motor is on the line.
Advanced Operating Functions
8.17 Synchronous Transfer
Control Manual
266
Operating Manual, A5E50491925A
Содержание SINAMICS PERFECT HARMONY GH180
Страница 2: ......
Страница 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Страница 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Страница 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...
Страница 516: ...List of abbreviations C 1 Symbols and Abbreviations NXGPro Control Manual 514 Operating Manual A5E50491925A ...
Страница 517: ...Index D NXGPro Control Manual Operating Manual A5E50491925A 515 ...
Страница 518: ...Index NXGPro Control Manual 516 Operating Manual A5E50491925A ...
Страница 530: ...Glossary NXGPro Control Manual 528 Operating Manual A5E50491925A ...
Страница 537: ......
Страница 538: ... XUWKHU QIRUPDWLRQ ZZZ VLHPHQV FRP GULYHV 6LHPHQV QGXVWU QF 3 XQW 9DOOH 5RDG 1HZ HQVLQJWRQ 3 8QLWHG 6WDWHV RI PHULFD ...