11.12
Cell Faults and Alarms
11.12.1
Cell Faults/Alarms Prolog
Cell originating faults and alarms are logged by the PC board following a power cell fault
indication. These faults are available for inspection using one of the following methods
• through the keypad display
• uploaded to a PC via the serial port
• uploaded to a PC via the Drive Tool
All active cell faults and alarms are displayed on the keypad display. Use the arrow keys to scroll
up and down through the faults. Use the alarm/fault log upload function (6230) in the alarm/
fault log menu (6210) to upload the log to a PC for analysis and for sending to the appropriate
Siemens or plant personnel.
All cell faults are generated by circuitry located on the cell control board (CCB) of each power cell
and are received by the microprocessor board through circuitry on the digital modulator. Use the
following table as a quick troubleshooting guide to locate the cause of the fault condition. This
table lists faults that may occur in all SINAMICS PERFECT HARMONY GH180 drives unless
otherwise noted. All cell faults are initiated by the CCB located in each power cell
Handling Specific (Individual) Cell Faults
Table 11-13 Specific (individual) cell faults
Fault display
Type
Enable
Potential causes and corrective actions
xx 2Q Diode shorted
xx = cell that is faulted
F
Fixed
Cause
The cell has sensed that a diode is in a short circuit condition.
Action
The cell needs to be replaced. The drive cannot operate with a short-
circuited diode, medium voltage will be disconnected.
xx Diode or Phase Open
xx = cell that is faulted
F
Fixed
Cause
The cell has sensed that either a diode has failed in an open condition, or
a cell single-phase condition was detected. In either case the cell will issue
an Alarm and it can continue to run, however it is recommended to reduce
the power.
Action
1. It is recommended to verify if input cell fuses are not open.
2. If the diode has failed it is recommended to have the cell repaired or
replaced.
Troubleshooting Faults and Alarms
11.12 Cell Faults and Alarms
Control Manual
466
Operating Manual, A5E50491925A
Содержание SINAMICS PERFECT HARMONY GH180
Страница 2: ......
Страница 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Страница 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Страница 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...
Страница 516: ...List of abbreviations C 1 Symbols and Abbreviations NXGPro Control Manual 514 Operating Manual A5E50491925A ...
Страница 517: ...Index D NXGPro Control Manual Operating Manual A5E50491925A 515 ...
Страница 518: ...Index NXGPro Control Manual 516 Operating Manual A5E50491925A ...
Страница 530: ...Glossary NXGPro Control Manual 528 Operating Manual A5E50491925A ...
Страница 537: ......
Страница 538: ... XUWKHU QIRUPDWLRQ ZZZ VLHPHQV FRP GULYHV 6LHPHQV QGXVWU QF 3 XQW 9DOOH 5RDG 1HZ HQVLQJWRQ 3 8QLWHG 6WDWHV RI PHULFD ...