Order
Code
Meaning
Description
5
T OL
Thermal overload rollback
The drive has limited the amount of torque produced to prevent thermal
overload of the input transformer.
6
F WK
Field weakening rollback
This condition exists when the motor flux is low and the application re‐
quires high torque. This prevents "motor pull-out", an unstable operating
condition of the motor, by decreasing the motor torque until flux is re-
established in the motor.
7
C OL
Cell overload rollback
A cell current overload model has calculated a thermal overload condition
of the drive cells and the drive has limited the amount of torque allowable.
8
NET1
Network 1 limit
Torque limited by network 1 setting.
9
NET2
Network 2 limit
Torque limited by network 2 setting.
10
ALIM
Analog torque Limit
Torque limited by analog input.
11
EALM
External analog Limit
Drive is in torque limit due to external analog limit when in torque mode.
12
ENLM
External network Limit
Drive is in torque limit due to external network limit when in torque mode.
13
EMLM
External menu Limit
Drive is in torque limit due to external menu limit when in torque mode.
14
CIMB
Cell imbalance Limit
AFE cells in regen limit when the sum of the three phase voltage gains
exceed 3 pu. Each phase voltage gain is equal to the number of installed
cells per phase, divided by the active cells in that phase.
15
RLBK
Roll back
Appears during acceleration if drive has reached its torque limit setting.
16
RGEN
Regeneration
During normal deceleration, this message will be displayed when the drive
is operating in regen torque limit.
17
BRKG
Dual frequency braking
Appears while drive is decelerating with dual frequency braking enabled.
18
OVLT
Regen Limit for 6-step
Indicates that the six-step regeneration torque limit is in effect. It is set
when the cell voltage gets too high, and serves to reduce the regen torque
limit to limit the energy flow from the output (motor) to the cells to pre‐
vent overvoltaging the cells.
19
BYPS
Cell bypassed
Indicates that one or more cells are in bypass.
20
PRCH
Pre-charge
One of the pre-charge modes is selected and the drive is pre-charging, or
ready to pre-charge.
21
OLTM
Open loop test mode
Appears if drive control algorithm is set to open loop test mode.
22
MODE
Normal mode display
This is the typical display message during normal operation.
23
CURP
Current profile mode limit
Appears if the current limit is due to the current profile limit curve.
Table 9-16
Line 2 of mode field
Order
Code
Meaning
Description
1
NOMV
No medium voltage
No input line voltage detected.
2
INH
CR3 inhibit
The CR3 or "drive inhibit" input is asserted.
3
OFF
Idle state
The drive is ready to run but is in an idle state.
4
MAGN
Magnetizing motor state
The drive is magnetizing the motor or passing through the magnetizing
drive state.
5
SPIN
Spinning load state
The drive is trying to detect the speed of the motor in order to synchronize
the drive frequency.
6
UXFR
Up transfer state
The drive is in the "Up Transfer State" preparing to transfer the motor to the
input line.
7
DXFR
Down transfer state
The drive is in the "Down Transfer State" preparing to transfer the motor
from the input line to the drive.
Software user interface
9.6 ML Keypad
Control Manual
Operating Manual, A5E50491925A
425
Содержание SINAMICS PERFECT HARMONY GH180
Страница 2: ......
Страница 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Страница 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Страница 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...
Страница 516: ...List of abbreviations C 1 Symbols and Abbreviations NXGPro Control Manual 514 Operating Manual A5E50491925A ...
Страница 517: ...Index D NXGPro Control Manual Operating Manual A5E50491925A 515 ...
Страница 518: ...Index NXGPro Control Manual 516 Operating Manual A5E50491925A ...
Страница 530: ...Glossary NXGPro Control Manual 528 Operating Manual A5E50491925A ...
Страница 537: ......
Страница 538: ... XUWKHU QIRUPDWLRQ ZZZ VLHPHQV FRP GULYHV 6LHPHQV QGXVWU QF 3 XQW 9DOOH 5RDG 1HZ HQVLQJWRQ 3 8QLWHG 6WDWHV RI PHULFD ...