Note
Tripped Pre-charge Circuit Breaker Occurrences
The pre-charge circuit breaker shall be tripped if any of the following occurs:
• Over-voltage (>115%) occurs during pre-charge
• Under-Voltage Trip (PCVMRStatus_O)
• Input Protection Fault
• LFR Trip
• PB4/E-Stop
• M2 Contactor Open Status Failure
• Trip_CB2 (TripPrechargeCB2_O) is asserted
The SOP input control flags below are available for particular cell types using the pre-charge
function by selecting Type 4 pre-charge. No dedicated inputs are used.
Table 5-3
Type 4 SOP Input Control Flags
Flag
Function
Description
StartCellPrecharge_O
PrechargeRequest
Request to start pre-charge
PrechargeM2CloseAck_O
M2CloseACK
Feedback of M2 contact
PrechargeM1CloseAck_O
M1CloseACK
Feedback of M1 contact
TripPrechargeCB2_O (SOP)
TripPrechargeCB2
Request trip of pre-charge CB
PCVMRStatus_O
PCVMRStatus
Precharge voltage (CB UV trip) status - '1' = voltage okay
CB2Status_O
CB2Status
Precharge CB status - '1' = CB is closed
There are 16 digital outputs on the first user I/O board:
• DO-0 to DO-15
There is one digital output on the system interface board:
• SIB M1 DOUT
Table 5-4
Type 4 Dedicated and SOP Outputs
Dedicated Output*
Terminal
SOP Feedback
Function
Description
DO-14
J4-7, 8, 9
CIMVType4
CIMV
Command to close M1
PrechargeM2Close_I
Assigned out‐
put
SOP determined
M2Close
Command to close M2
OpenPrechargeCB_I
Assigned out‐
put
SOP determined
BreakerTrip
Command to open (trip) pre-charge supply
breaker
M1 DOUT
SIB 51, 53, 55 M1Permit‐
Closed_I
M1Close
Permissive
(TIMV)
If this signal is de-energized, the drive’s medi‐
um voltage will trip immediately.
If the signal is not energized, it will be an in‐
hibit.
* Dedicated Output: Refer to specific drive wiring diagram for dedicated output designations
Hardware User Interface Description
5.3 User Accessible Interfaces
Control Manual
78
Operating Manual, A5E50491925A
Содержание SINAMICS PERFECT HARMONY GH180
Страница 2: ......
Страница 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Страница 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Страница 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...
Страница 516: ...List of abbreviations C 1 Symbols and Abbreviations NXGPro Control Manual 514 Operating Manual A5E50491925A ...
Страница 517: ...Index D NXGPro Control Manual Operating Manual A5E50491925A 515 ...
Страница 518: ...Index NXGPro Control Manual 516 Operating Manual A5E50491925A ...
Страница 530: ...Glossary NXGPro Control Manual 528 Operating Manual A5E50491925A ...
Страница 537: ......
Страница 538: ... XUWKHU QIRUPDWLRQ ZZZ VLHPHQV FRP GULYHV 6LHPHQV QGXVWU QF 3 XQW 9DOOH 5RDG 1HZ HQVLQJWRQ 3 8QLWHG 6WDWHV RI PHULFD ...