and event logs. This fault does not cause the removal of the MV power, it records the event after
the fact. Refer to Section System Arc Detection of Chapter Operating the Control for information
about this safety feature.
Table 11-17 Cooling Related
Fault Display
Type
Enable
Potential Causes and Corrective Actions
One Blower Not Avail
A
SOP
Cause
Drive initiated alarm set when the
OneBlowerLost_O
SOP
flag is set true and the alarm is enabled by
setting
OneBlowerLost_EN_O
true. On an air cooled drive,
when one of either of the cell blowers or transformer blowers
is not functioning, this is triggered via the SOP. This is part of
the Standard SOP for air cooled drives.
Action
1. Check physical input connected to SOP flag.
2. Check for faulty blowers or obstruction.
All Blowers Not Avail
F/A
SOP
Cause
Drive initiated alarm or fault when
AllBlowerLost_O
SOP
flag is set true and the alarm/fault is enabled by setting
the
AllBlowerLostEn_O
flag true. This defaults to a fault
with no way to change to a warning with this release. If an
alarm is desired, then the flag
AllBlowersLostWn_O
must
also be set true. This is triggered by the SOP when 2 of 3 cell
banks or both transformer banks of blowers is not function‐
ing. This is primarily used as a trip alarm preceding an over
temperature trip, used on air cooled drives as part of the
Standard SOP.
Action
1. Check physical input connected to SOP flag.
2. Check for faulty blowers or obstruction.
Clogged Filters
F/A
SOP
Cause
Drive initiated fault/alarm when the
CloggedFilters_O
SOP flag is set true and the
CloggedFiltersEn_O
flag is
set true to enable it. The default is a fault. If you desire an
alarm, then the flag
CloggedFiltersWn_O
must be set
true. This is used when an air filter becomes clogged to warn
of reduced air flow. This is not part of the Standard SOP.
Action
1. Check physical input connected to SOP flag.
2. Change filter or check for obstruction.
NOTE: On more recent drives a separate PLC controls the cooling. refer to that documentation if this is the case. The
following faults will not occur within the drive if a separate cooling PLC is used.
Troubleshooting Faults and Alarms
11.13 Dedicated I/O for Input Protection
Control Manual
488
Operating Manual, A5E50491925A
Содержание SINAMICS PERFECT HARMONY GH180
Страница 2: ......
Страница 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Страница 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Страница 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...
Страница 516: ...List of abbreviations C 1 Symbols and Abbreviations NXGPro Control Manual 514 Operating Manual A5E50491925A ...
Страница 517: ...Index D NXGPro Control Manual Operating Manual A5E50491925A 515 ...
Страница 518: ...Index NXGPro Control Manual 516 Operating Manual A5E50491925A ...
Страница 530: ...Glossary NXGPro Control Manual 528 Operating Manual A5E50491925A ...
Страница 537: ......
Страница 538: ... XUWKHU QIRUPDWLRQ ZZZ VLHPHQV FRP GULYHV 6LHPHQV QGXVWU QF 3 XQW 9DOOH 5RDG 1HZ HQVLQJWRQ 3 8QLWHG 6WDWHV RI PHULFD ...