Cell Bypass COM Fail
F
Fixed
Cause
The control system is not communicating with the MV bypass board. By‐
pass is in use.
Action
1. Verify the fiber optic connection between the DCR and MV bypass
board is intact.
2. Replace MV bypass board.
3. Replace DCR.
Cell Bypass Acknowledge
F
Fixed
Cause
The control issued a command to bypass a cell, but the MV bypass board
did not return an acknowledgement.
Action
1. Verify that the bypass contactor is working properly.
2. Check wiring between MV bypass board and contactor.
3. Replace MV bypass board or contactor.
Cell Bypass Link
F
Fixed
Cause
The control system is not communicating with the MV bypass board, i.e.
the MV bypass board is either not receiving commands, or is getting parity
errors in the messages from the modulator. Bypass is in use.
Action
Refer to Cell bypass COM fail above.
Cell Bypass COM Alarm
A
Fixed
Cause
The control system is not communicating with the MV bypass board, but
the bypass system is not in use.
Action
Refer to Cell bypass COM fail above.
Cell Bypass Link Alarm
A
Fixed
Cause
The modulator is not communicating with the MV bypass board, but the
bypass system is not in use.
Action
Refer to Cell bypass COM fail above.
Cell Bypass Fault
F
Fixed
Cause
The cell failed to go into bypass when commanded to do so.
Action
1. Check bypass system and contactor MV bypass board.
2. Refer to Cell bypass COM fail above.
Troubleshooting Faults and Alarms
11.11 Drive Faults and Alarms Cell Bypass Related
Control Manual
464
Operating Manual, A5E50491925A
Содержание SINAMICS PERFECT HARMONY GH180
Страница 2: ......
Страница 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Страница 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Страница 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...
Страница 516: ...List of abbreviations C 1 Symbols and Abbreviations NXGPro Control Manual 514 Operating Manual A5E50491925A ...
Страница 517: ...Index D NXGPro Control Manual Operating Manual A5E50491925A 515 ...
Страница 518: ...Index NXGPro Control Manual 516 Operating Manual A5E50491925A ...
Страница 530: ...Glossary NXGPro Control Manual 528 Operating Manual A5E50491925A ...
Страница 537: ......
Страница 538: ... XUWKHU QIRUPDWLRQ ZZZ VLHPHQV FRP GULYHV 6LHPHQV QGXVWU QF 3 XQW 9DOOH 5RDG 1HZ HQVLQJWRQ 3 8QLWHG 6WDWHV RI PHULFD ...