7.11.3
Set Point Sources
Set points are internal menu entries that are static values based on user entry, keypad settings,
or remote demand from a network communication interface. There are a total of eight inputs
that are menu entries from remote communications. There are two additional entries that are
reserved for safety override and jog level set points.
• Keypad
– Use front panel keypad or ToolSuite software to set speed demand.
• Increment/decrement (sample and hold)
– 2 digital inputs that increase/decrease raw speed demand at the active acceleration/
deceleration rate, while input is maintained. When the input is released, the current value
is maintained.
• Increment/Decrement Step
– 6 digital inputs that provide programmable step change to output demand each time
input transitions from low to high state.
• Preset levels
– Multiple user-defined preset values via menu system.
• Jog
– Set to maximum active speed limit, intended for test purposes to "bump" motor.
• Communication Network
– Digital value as set per external communication interface to a PLC/DCS.
7.11.4
Speed Profile
The speed profile uses the velocity demand signal as input, and generates a modified best fit
straight line (BFSL) velocity demand output.
Parameter for the Speed Profile
Refer to Speed Profile Menu (4000) in Section Options for Auto Menu (4) of Chapter Parameter
Assignment / Addressing for parameters to set the speed profile and for further description of
speed profiling control.
7.11.5
Critical Speed Avoidance
Critical speed avoidance is used to prohibit the drive from operating in frequency ranges that
may cause resonant frequencies in mechanical systems. The control provides three independent
avoidance bands.
The critical frequency feature, also known as resonance avoidance, is accomplished using skip
frequencies and skip bands, as illustrated in the following figure.
Operating the Control
7.11 Command Generator
Control Manual
220
Operating Manual, A5E50491925A
Содержание SINAMICS PERFECT HARMONY GH180
Страница 2: ......
Страница 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Страница 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Страница 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...
Страница 516: ...List of abbreviations C 1 Symbols and Abbreviations NXGPro Control Manual 514 Operating Manual A5E50491925A ...
Страница 517: ...Index D NXGPro Control Manual Operating Manual A5E50491925A 515 ...
Страница 518: ...Index NXGPro Control Manual 516 Operating Manual A5E50491925A ...
Страница 530: ...Glossary NXGPro Control Manual 528 Operating Manual A5E50491925A ...
Страница 537: ......
Страница 538: ... XUWKHU QIRUPDWLRQ ZZZ VLHPHQV FRP GULYHV 6LHPHQV QGXVWU QF 3 XQW 9DOOH 5RDG 1HZ HQVLQJWRQ 3 8QLWHG 6WDWHV RI PHULFD ...