Parameters for High Starting Torque Mode
High starting torque mode is selected internally when either PMM or SMDC is selected as the
control mode.
Refer to High Starting Torque Menu (2960) in Section Options for Drive Menu (2) of Chapter
Parameter Assignment / Addressing for parameters associated with this function.
For long cable applications, set the "Minimum Speed Limit" to approximately the same as the
percent value of the total resistance in series with the motor. For example, if a long cable
application has the total series resistance at about 30 % of motor base impedance, set a
minimum speed limit of 30 % or higher.