Fault display
Type
Enable
Potential causes and corrective actions
xx Link
xx = cell that is faulted
F
Fixed
Cause
A faulted cell indicates a cell communication link failure. The cell failed to
respond to a modulator command packet.
Action
1. Check the fiber optic cable connection on both ends.
2. Cell may need to be serviced.
3. Change fiber optic cable.s
4. Change CCB.
5. Contact Siemens customer service.
xx Communication
xx = cell that is faulted
F
Fixed
Cause
An error in the optical communications from the modulator was detected
by a cell. Typically this fault is a result of a parity error caused by noise, but
can also be a time-out error caused by a faulty communications channel
on the CCB.
Action
1. Check fiber connections.
2. Cell might need to be serviced.
3. Change fiber.
4. Change CCB.
5. Contact Siemens customer service.
xx Control Fuse Blown
xx = cell that is faulted
F
Fixed
Cause
Cell control power fuse blown. This is rarely seen since the CCB has a dual
source of power.
Action
Check cell fuses, replace if necessary.
xx DC Bus Low Warning
xx = cell that has alarm
A
Fixed
Cause
Cell DC bus is below alarm level. This fault alarm applies to water-cooled
6SR325, LNG, or HV cells only.
Action
Check for single phase input, low input line conditions, blown input fuses.
xx AC Vav Low Warning
xx = cell that has alarm
A
Fixed
Cause
Cell AC input is below alarm level. CCB sets alarm level and comes back
from the cell as
/ Vavail_ok
internal flag in all cells except water-
cooled 6SR325, LNG, and HV.
Action
1. Check for single phase input, low input line conditions, blown input
fuses.
2. Check for CCB failure.
Troubleshooting Faults and Alarms
11.12 Cell Faults and Alarms
Control Manual
Operating Manual, A5E50491925A
471
Содержание SINAMICS PERFECT HARMONY GH180
Страница 2: ......
Страница 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Страница 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Страница 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...
Страница 516: ...List of abbreviations C 1 Symbols and Abbreviations NXGPro Control Manual 514 Operating Manual A5E50491925A ...
Страница 517: ...Index D NXGPro Control Manual Operating Manual A5E50491925A 515 ...
Страница 518: ...Index NXGPro Control Manual 516 Operating Manual A5E50491925A ...
Страница 530: ...Glossary NXGPro Control Manual 528 Operating Manual A5E50491925A ...
Страница 537: ......
Страница 538: ... XUWKHU QIRUPDWLRQ ZZZ VLHPHQV FRP GULYHV 6LHPHQV QGXVWU QF 3 XQW 9DOOH 5RDG 1HZ HQVLQJWRQ 3 8QLWHG 6WDWHV RI PHULFD ...