2.4
Safety Information and Warnings (750A and M57)
DANGER
Hazardous Voltage!
• Always follow the proper lock-out/tag-out procedures before beginning any maintenance
or troubleshooting work on the VFD.
• Always follow standard safety precautions and local codes during installation of external
wiring. The installation must follow wiring practices and insulation systems as specified in
IEC 61800-5-1.
• Hazardous voltages may still exist within the VFD cabinets even when the disconnect
switch is open (off) and the supply power is shut off.
• Only qualified individuals should install, operate, troubleshoot, and maintain this VFD. A
qualified individual is "a person, who is familiar with the construction and operation of the
equipment and the hazards involved."
• Always work with one hand, wear electrical safety gloves, wear insulated electrical hazard
rated safety shoes, and safety goggles. Also, always work with another person present.
• Always use extreme caution when handling or measuring components that are inside the
enclosure. Be careful to prevent meter leads from shorting together or from touching other
terminals.
• Use only instrumentation (e.g., meters, oscilloscopes, etc.) intended for high voltage
measurements (that is, isolation is provided inside the instrument, not provided by isolating
the chassis ground of the instrument).
• Never assume that switching off the input disconnector will remove all voltage from
internal components. Voltage is still present on the terminals of the input disconnector.
Also, there may be voltages present that are applied from other external sources.
• Never touch anything within the VFD cabinets until verifying that it is neither thermally hot
nor electrically alive.
• Never remove safety shields (marked with a HIGH VOLTAGE sign) or attempt to measure
points beneath the shields.
• Never operate the VFD with cabinet doors open. The only exception is the control cabinet
which contains extra low voltages (ELV).
• Never connect any grounded (i.e., non-isolated) meters or oscilloscopes to the system.
• Never connect or disconnect any meters, wiring, or printed circuit boards while the VFD is
energized.
• Never defeat the instrument’s grounding.
• When a system is configured with VFD bypass switchgear (e.g. contactors between line and
motor, and VFD and motor), these switches should be interlocked so that the line voltage
is never applied to the VFD output if the medium input voltage is removed from the VFD.
Safety notes
2.4 Safety Information and Warnings (750A and M57)
Control Manual
26
Operating Manual, A5E50491925A
Содержание SINAMICS PERFECT HARMONY GH180
Страница 2: ......
Страница 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Страница 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Страница 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...
Страница 516: ...List of abbreviations C 1 Symbols and Abbreviations NXGPro Control Manual 514 Operating Manual A5E50491925A ...
Страница 517: ...Index D NXGPro Control Manual Operating Manual A5E50491925A 515 ...
Страница 518: ...Index NXGPro Control Manual 516 Operating Manual A5E50491925A ...
Страница 530: ...Glossary NXGPro Control Manual 528 Operating Manual A5E50491925A ...
Страница 537: ......
Страница 538: ... XUWKHU QIRUPDWLRQ ZZZ VLHPHQV FRP GULYHV 6LHPHQV QGXVWU QF 3 XQW 9DOOH 5RDG 1HZ HQVLQJWRQ 3 8QLWHG 6WDWHV RI PHULFD ...