Table 6-12
Speed Ramp Setup Menu (2260) Parameters
Parameter
ID
Unit
Default
Min
Max
Description
Accel time 1
2270
sec
5.0
0.0
3200.0
Acceleration time 1 in seconds from zero to
rated speed.
Decel time 1
2280
sec
5.0
0.0
3200.0
Deceleration time 1 in seconds from rated to
zero speed.
Accel time 2
2290
sec
5.0
0.0
3200.0
Acceleration time 2 in seconds from zero to
rated speed.
Decel time 2
2300
sec
5.0
0.0
3200.0
Deceleration time 2 in seconds from rated to
zero speed.
Accel time 3
2310
sec
5.0
0.0
3200.0
Acceleration time 3 in seconds from zero to
rated speed.
Decel time 3
2320
sec
5.0
0.0
3200.0
Deceleration time 3 in seconds from rated to
zero speed.
Jerk rate
2330
0.1
0.0
3200.0
Jerk rate in time to reach an acceleration rate
that will achieve rated velocity in 1 sec.
Table 6-13
Critical Frequency Menu (2340) Parameters
Parameter
ID
Unit
Default
Min
Max
Description
Skip center freq 1 2350
Hz
15.0
0.0
360.0
Enter the center of the first critical frequency
band to be avoided.
Skip center freq 2 2360
Hz
30.0
0.0
360.0
Enter the center of the second critical fre‐
quency band to be avoided.
Skip center freq 3 2370
Hz
45.0
0.0
360.0
Enter the center of the third critical frequen‐
cy band to be avoided.
Skip bandwidth
1
2380
Hz
0.0
0.0
6.0
Enter the bandwidth of the first critical fre‐
quency band to be avoided.
Skip bandwidth
2
2390
Hz
0.0
0.0
6.0
Enter the bandwidth of the second critical
frequency band to be avoided.
Skip bandwidth
3
2400
Hz
0.0
0.0
6.0
Enter the bandwidth of the third critical fre‐
quency band to be avoided.
Table 6-14
Spinning Load Menu (2420) Parameters
Parameter
ID
Unit
Default
Min
Max
Description
Spinning load
mode*
2430
Off
Enable or disable spinning load and set the
direction of frequency scans:
• Off
• Forward
• Reverse
• Both; scans first in the forward direction,
then in the reverse direction.
Scan end thresh‐
old
2440
%
20.0
1.0
50.0
The point where scan ends if motor flux is
above this level, as a percentage of motor
rated flux.
Parameter Assignment/Addressing
6.5 Options for Drive Menu (2) - first part
Control Manual
Operating Manual, A5E50491925A
105
Содержание SINAMICS PERFECT HARMONY GH180
Страница 2: ......
Страница 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Страница 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Страница 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...
Страница 516: ...List of abbreviations C 1 Symbols and Abbreviations NXGPro Control Manual 514 Operating Manual A5E50491925A ...
Страница 517: ...Index D NXGPro Control Manual Operating Manual A5E50491925A 515 ...
Страница 518: ...Index NXGPro Control Manual 516 Operating Manual A5E50491925A ...
Страница 530: ...Glossary NXGPro Control Manual 528 Operating Manual A5E50491925A ...
Страница 537: ......
Страница 538: ... XUWKHU QIRUPDWLRQ ZZZ VLHPHQV FRP GULYHV 6LHPHQV QGXVWU QF 3 XQW 9DOOH 5RDG 1HZ HQVLQJWRQ 3 8QLWHG 6WDWHV RI PHULFD ...