Technical Specifications
A-3
Point-to-point connection CP 440 Installation and Parameter Assignment
A5E00057742-02
Technical Specifications of the X27 (RS 422/485) Interface
The table below contains the technical specifications of the X27 (RS 422/ 485)
interface of the CP 440-RS 422/485.
Table A-1
Technical Specifications of the X27 (RS 422/485) Interface
Technical Specifications
Interface
RS 422 or RS 485, 15-pin subminiature D female connector
RS 422 signals
RS 485 signals
TXD (A), RXD (A), TXD (B), RXD (B), GND
R/T (A), R/T (B), GND
All isolated against the S7-internal power supply (backplane
bus) and the external 24V DC power supply
Max. transmission link
1200 m
Max. transmission rate
115200 bps
Technical Specifications of the 3964(R) Procedure
The following table contains the general technical specifications of the 3964(R)
procedure.
Table A-2
Technical Specifications of the 3964(R) Procedure
3964(R) Procedure with Default Values
Max. message
frame length
200 bytes
Parameters
The following can be parameterized:
•
With/without a block check character
•
Priority: low/high
•
Transmission rate: 300, 600, 1200, 2400, 4800, 9600, 19200,
38400, 57600, 76800, 115200 bps
•
Character frame: 9, 10, 11 or 12 bits
•
Initial state of the receive line: none, R(A)5V/R(B)0V, R(A)0V/R(B)5V
•
Number of message frames to be buffered: 1 to 10, use entire buffer
3964(R) Procedure, Parameterizable
Max. message
frame length
200 bytes
Parameters
The following can be parameterized:
•
With/without a block check character
•
Priority: low/high
•
Transmission rate: 300, 600, 1200, 2400, 4800, 9600, 19200,
38400, 57600, 76800, 115200 bps
•
Character frame: 9, 10, 11 or 12 bits
•
Character delay time: 20 ms to 65535 ms at intervals of 10 ms
•
Acknowledgment delay time: 20 ms to 65535 ms at intervals of
10 ms
•
Number of setup attempts: 1 to 255
•
Number of transmission attempts: 1 to 255
•
Initial state of the receive line: none, R(A)5V/R(B)0V, R(A)0V/R(B)5V