Communication Using Function Blocks
6-12
Point-to-point connection CP 440 Installation and Parameter Assignment
A5E00057742-02
Parameters of the RECV_440 FB
The following table lists the parameters of the RECV_440 FB.
Table 6-3
Parameters of the RECV_440 FB
Name
Type
Data Type
Comment
Permitted Values,
Comment
EN_R
INPUT
BOOL
Enables reading of data
R
INPUT
BOOL
Aborts job
Current job is aborted. Receiving
is disabled.
LADDR
INPUT
INT
Basic address of CP 440
The basic address can be found
in the configuration table in
STEP 7.
DB_NO
INPUT
INT
Data block number
Receive DB No.:
CPU-specific, zero is not
allowed
DBB_NO
INPUT
INT
Data byte number
Offset is CPU-specific
NDR
1
OUTPUT
BOOL
Job completed without
errors, data accepted
STATUS parameter == 16#00;
ERROR
1
OUTPUT
BOOL
Job completed with errors
STATUS parameter contains
error details
LEN
1
OUTPUT
INT
Length of message frame
received
1
LEN
200, specified
in number of bytes
STATUS
1
OUTPUT
WORD
Specification of the error
If ERROR == 1, STATUS
parameter contains error
information
1
The parameter is available until the next call of the FB!