Technical Specifications
A-5
Point-to-point connection CP 440 Installation and Parameter Assignment
A5E00057742-02
A.2
Transmission Times
Transmission Times
The tables below indicate the transmission times required depending on the
transmission protocol selected.
Two S7-400s each with a CPU 416 (6ES7 416-2XK02-0AB0) and a CP 440 were
used to measure the times. A SEND_440 FB was programmed in the user
program of the active CPU, and a RECV_440 FB was programmed in the user
program of the passive CPU. The time that elapsed between the initiation and
completion of the job was measured.
ASCII Driver
Transmission times with the ASCII driver:
Table A-3
Transmission Times with the ASCII Driver in ms
Baud rate
(bps)
User data
115200
76800
57600
38400
19200
9600
4800
2400
1200
600
300
1 byte
1.5
2
2
2
3
4
8
15
29
55
110
10 bytes
2
2
3
5
8
14
28
56
111
220
440
20 bytes
4
5
6
8
14
26
52
102
202
404
807
50 bytes
6
9
12
17
32
60
120
240
478
952
1906
100 bytes
12
17
22
32
61
118
236
470
936
1872
3740
200 bytes
22
32
41
59
117
230
460
920
1835
3668
7330