Connecting Cables
B-4
Point-to-point connection CP 440 Installation and Parameter Assignment
A5E00057742-02
Connecting Cable for X 27 (S7/M7 (CP
440) – CP
340/CP 341/CP 440/CP 441)
The figure below illustrates the connecting cable for a point-to-point connection
between a CP 440 and a CP 340/CP 341/CP 440/CP 441 for RS 422 operation.
For the connecting cables you require the following male connectors:
•
At the CP 440 end: 15-pin subminiature D male connector with a screw fixing
•
At the communication partner: 15-pin subminiature D male with a screw fixing
CP 440
Communication partner
Receiver
Receiver
Sender
Sender
2
T(A)–
R(A)
4
9
T(B)+
R(B)
11
4
R(A)– T(A)
2
Casing shield
Casing shield
8
GND
GND
8
Shield
Cable type
LIYCY 3 x 2 x 0.14.
T(A)/T(B) and R(A)/R(B)
twisted pairs.
11
R(B)+ T(B)
9
1)
1) In the case of cables longer than 50 m you must solder in a terminating
resistor of approx. 330
on the receiver for trouble-free traffic.
1)
Figure B-1
X27 Connecting Cable for CP 440 – CP 340/CP 341/CP 440/CP 441 for
RS 422 Operation (Four-Wire)
The connecting cable is available under the order number (6ES7 902-3...) specified
in Appendix D.
Note
This cable type can be used in the following lengths for the CP 440 as a
communication partner:
Max. 1200 m at 19 200 bps
Max. 500 m at 38 400 bps
Max. 200 m at 115 200 bps