Communication Using Function Blocks
6-16
Point-to-point connection CP 440 Installation and Parameter Assignment
A5E00057742-02
Parameters of the RES_RECV FB
The following table lists the parameters of the RES_RECV FB.
Table 6-4
Parameters of the RES_RECV FB
Name
Type
Data Type
Comment
Permitted Values,
Comment
REQ
INPUT
BOOL
Initiates job with positive
edge
R
INPUT
BOOL
Aborts job
Current job is aborted. Sending
is disabled.
LADDR
INPUT
INT
Basic address of the
CP 440
The basic address is taken from
STEP 7.
DONE
1
OUTPUT
BOOL
Job completed without
errors
STATUS parameter == 16#00;
ERROR
1
OUTPUT
BOOL
Job completed with errors
STATUS parameter contains
error information
STATUS
1
OUTPUT
WORD
Specification of the error
If ERROR == 1, STATUS
parameter contains error
information
1
The parameter is available until the next call of the FB.