Configuring and Parameterizing the CP 440
5-5
Point-to-point connection CP 440 Installation and Parameter Assignment
A5E00057742-02
How is the Storage of the Received Message Frames Controlled by Setting the
“Reaction to CPU Stop” Parameter?
The response depends on whether or not flow control is used.
Table 5-3
Control of Message Frame Storage Without Flow Control
Without Flow Control
Saved Frames
Frame Just Arriving
New Message Frames
Reaction to CPU Stop:
Continue
Retained
Saved; discarded if the
buffer is full
Saved until the buffer is
full, then discarded
Reaction to CPU Stop:
STOP
Retained
Discarded
Discarded
Table 5-4
Control of Frame Storage with Flow Control
With Flow Control
Saved Frames
Frame Just Arriving
New Frames
Reaction to CPU Stop:
Continue
Retained
Saved; flow control is
activated if the buffer is
full.
Saved; flow control is
activated if the buffer is
full.
Reaction to CPU Stop:
STOP
Retained
Further data cannot be
received because flow
control is activated.
Further data cannot be
received because flow
control is activated.