Diagnostics with the CP 440
8-6
Point-to-point connection CP 440 Installation and Parameter Assignment
A5E00057742-02
Event Classes
The table below describes the various event classes and numbers.
Table 8-2
Event Classes and Event Numbers
Event Class 0 (00H):
“Startup of the CP”
Event No.
Event Text
Remedy
(00)01H
Initialization of the CP completed
–
(00)03H
Point-to-point parameters applied
–
(00)04H
Parameters already on the CP (times
identical)
–
(00)07H
CPU mode transition to STOP
–
(00)08H
CPU mode transition to RUN/STARTUP
–
Event Class 2 (02H):
“Initialization error”
Event No.
Event Text
Remedy
(02)01H
No parameters
Parameter memory empty or has unknown
contents
Load the interface parameters.
(02)04H
Impermissible character frame
Correct the impermissible parameter
assignment, load the parameters onto the
module, and carry out a cold restart.
(02)05H
Impermissible transmission rate
Correct the impermissible parameter
assignment, load the parameters onto the
module, and carry out a cold restart.
(02)0FH
Invalid parameterization detected at start of
parameterized communication. Interface
could not be parameterized
Correct invalid parameterization and restart.
(02)12H
Impermissible
•
Monitoring time
•
Character delay time
With 3964(R) only:
•
Acknowledgment delay time
Correct the impermissible parameter
assignment, load the parameters onto the
module, and carry out a cold restart.