Connecting Cables
B-6
Point-to-point connection CP 440 Installation and Parameter Assignment
A5E00057742-02
X 27 Connecting Cable (S7/M7 (CP
440) – CP
544, CP 524, CPU 928B, CPU 945,
CPU 948)
The figure below illustrates the connecting cable for a point-to-point connection
between a CP 440 and a CP 544, CP 524, CPU 928B, CPU 945, CPU 948 for
RS 422 operation.
For the connecting cables you require the following male connectors:
•
At the CP 440 end: 15-pin subminiature D male connector with a screw fixing
•
at the communication partner: 15-pin sub D male with clip fixing
CP 440
Communication partner
Receiver
Receiver
Sender
Sender
2
T(A)–
R(A)
4
9
T(B)+
R(B)
11
4
R(A)– T(A)
2
Casing shield
Casing shield
11
R(B)+ T(B)
9
8
GND
GND
8
Shield
Cable type
LIYCY 3 x 2 x 0.14.
T(A)/T(B) and R(A)/R(B)
twisted pairs.
1) In the case of cables longer than 50 m you must solder in a terminating
resistor of approx. 330
on the receiver for trouble-free traffic.
1)
1)
Figure B-3
X27 Connecting Cable CP 440 – CP 544, CP 524, CPU 928B, CPU 945,
CPU 948 for RS 422 Operation (Four-Wire Mode)