Connecting Cables
B-5
Point-to-point connection CP 440 Installation and Parameter Assignment
A5E00057742-02
Connecting Cable for X 27 (S7/M7 (CP
440) – CP
340/CP 341/CP 440/CP 441)
The figure below illustrates the connecting cable for a point-to-point connection
between a CP 440 and a CP 340/CP 341/CP 440/CP 441 for RS 485 operation.
For the connecting cables you require the following male connectors:
•
At the CP 440 end: 15-pin subminiature D male connector with a screw fixing
•
at the communication partner: 15-pin sub D male with screw fixing
CP 440
Communication partner
Sender
Receiver
Sender
Receiver
2
T(A)–
T(A)–
2
9
T(B)+
T(B)+
9
4
R(A)–
R(A)
4
Casing shield
Casing shield
11
R(B)+
R(B)
11
8
GND
GND
8
Shield
Cable type
LIYCY 3 x 2 x 0.14.
R(A)/R(B) twisted.
1) In the case of cables longer than 50 m you must solder in a terminating
resistor of approx. 330
on the receiver for trouble-free traffic.
1)
1)
Figure B-2
X27 Connecting Cable for CP 440 – CP 340/CP 341/CP 440/CP 441 for
RS 485 Operation (Two-Wire)